| Plan Review Notes For Permit 12040458 |
| Permit Number |
12040458 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-18 09:42:04 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | | 2010 FLORIDA RESIDENTIAL CODE. | | | | | | 1- FLAT ROOF: | | | A) SELECTED ASSEMBLY ON PAGE 34 OF 41 OF NOA 08-0924.14 | | | SUBMITTED IS LIMITED BY GENERAL LIMITATION #9. THIS | | | LIMITATION DOESN'T ALLOW ENHANCED FASTENING TO MEET THE | | | DESIGN PRESSURES FOR CORNER AND PERIMETER AREAS AS | | | REQUIRED BY SEC. R301.2.1.4.3. NEED TO SELECT ANOTHER | | | ASSEMBLY THAT IS LIMITED BY GENERAL LIMITATION #7, | | | WHICH ALLOWS ENHANCED FASTENING. | | | | | | B) PROVIDE SIGNED AND SEALED ENHANCED FASTENING | | | CALCULATIONS (RAS 117) AS REQUIRED BY GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|