Plan Review Notes
Plan Review Notes For Permit 12040458
Permit Number 12040458
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-18 09:42:04RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE.
  
 1- FLAT ROOF:
 A) SELECTED ASSEMBLY ON PAGE 34 OF 41 OF NOA 08-0924.14
 SUBMITTED IS LIMITED BY GENERAL LIMITATION #9. THIS
 LIMITATION DOESN'T ALLOW ENHANCED FASTENING TO MEET THE
 DESIGN PRESSURES FOR CORNER AND PERIMETER AREAS AS
 REQUIRED BY SEC. R301.2.1.4.3. NEED TO SELECT ANOTHER
 ASSEMBLY THAT IS LIMITED BY GENERAL LIMITATION #7,
 WHICH ALLOWS ENHANCED FASTENING.
  
 B) PROVIDE SIGNED AND SEALED ENHANCED FASTENING
 CALCULATIONS (RAS 117) AS REQUIRED BY GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712