| 2012-06-15 14:17:56 | 1590 NORTH FLORIDA MANGO ROAD |
| | PERMIT #12040446 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | *****ORIGINAL COMMENTS HAVE NOT BEEN ADDRESSED***** |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL |
| | DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | MANUAL FLUSH BOLTS ARE NOT PERMITTED ON EGRESS DOORS. |
| | |
| | FOR DOORS EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE, NO |
| | OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE |
| | RELEASED BY THE PANIC/FIRE HARDWARE. |
| | |
| | SEVERAL SHEETS INCORRECTLY MAKE CODE REFERENCES TO AN |
| | "M" (MERCANTILE) OCCUPANCY. |
| | |
| | COORDINATE THE DOUBLE DOOR SWING DIRECTION OF THE |
| | STORAGE ROOM BETWEEN DRAWINGS. THE LIFE SAFETY DRAWING |
| | SHOWS A SWING DIRECTION OPPOSITE FROM THE OTHER PLANS. |
| | |
| | THE MEPF PLANS ARE NOT SIGNED OR SEALED BY THE |
| | PROFESSIONAL ENGINEER. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND FIRE ALARM SYSTEM. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |