2012-06-15 14:17:561590 NORTH FLORIDA MANGO ROAD
 PERMIT #12040446
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****ORIGINAL COMMENTS HAVE NOT BEEN ADDRESSED*****
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 MANUAL FLUSH BOLTS ARE NOT PERMITTED ON EGRESS DOORS.
  
 FOR DOORS EQUIPPED WITH PANIC OR FIRE EXIT HARDWARE, NO
 OTHER LOCKS OR LATCHES ARE PERMITTED THAT WOULD NOT BE
 RELEASED BY THE PANIC/FIRE HARDWARE.
  
 SEVERAL SHEETS INCORRECTLY MAKE CODE REFERENCES TO AN
 "M" (MERCANTILE) OCCUPANCY.
  
 COORDINATE THE DOUBLE DOOR SWING DIRECTION OF THE
 STORAGE ROOM BETWEEN DRAWINGS. THE LIFE SAFETY DRAWING
 SHOWS A SWING DIRECTION OPPOSITE FROM THE OTHER PLANS.
  
 THE MEPF PLANS ARE NOT SIGNED OR SEALED BY THE
 PROFESSIONAL ENGINEER.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE