2012-06-26 15:24:56BUILDING PLAN REVIEW
 PERMIT: 12040446
 ADD: 1590 FLORIDA MANGO RD
 CONT: ROUND HILL DEVELOPMENT GROUP
 TEL: (561)718-0831
  
 2007 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) COMPLIED.
  
 2)COMPLIED.
  
 3) SEMI COMPLIED. SHEET A-2 AND LS SHEETS NEED TO SHOW
 DOOR SWING IN THE SAME DIRECTION. SHEET A-2 DOES NOT
 INDICATE OCCUPANCY SEPERATION BETWEEN THE ASSEMBLY AND
 STORAGE OCCUPANCY, PLEASE PROVIDE COMPLIANCE WITH 2010
 FBC-B TABLE 508.3.3 AND OPENING PROTECTIVES (DOORS) PER
 TABLE 715.4.
  
 4) SHEET A--2A INDICATES NEW A/C EQUIPMENT ON CONCRETE
 PADS AT A ELEVATION OF 13.5'. NOTE THIS IS THE MINIMUM
 BASE FLOOD ELEVATION FOR SLABS LOCATED IN A FLOOD ZONE.
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED
 BEFORE:
 1) PERMIT ISSUANCE.
 2) AFTER SLAB IS POURED
 3) BEFORE ISSUANCE OF CERTIFICATE OF OCCUPANCY.
 SUBMITTED ELEVATION CERTIFICATE INDICATES SEE SECTION
 "C" FINISHED CONSTRUCTION.
 THIS IS A NEW PROJECT AND THE DOCUMENT SHOULD BE
 CHECKED "CONSTRUCTION DOCUMENTS" NOT FINISHED
 CONSTRUCTION.
  
 FEMA ELEVATION CERTIFICATE SECTION C (E) MISSING
 COMMENT SECTION DESCRIBE TYPE OF EQUIPMENT AND LOCATION
 IN COMMENTS BACK OF SHEET, MISSING.
  
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 MARCH 31, 2012.
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS
 NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES
 MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED
 ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW
 FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 5) COMPLIED.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 7) SEE SHEET A-2 HARDWARE SCHEDULE AND USE OF MANUAL
 FLUSH BOLTS WITHIN THE HARDWARE SCHEDULE.
  
 1008.1.8.4 BOLT LOCKS. MANUALLY OPERATED FLUSH BOLTS OR
 SURFACE BOLTS ARE NOT PERMITTED. ALL HARDWARE MUST BE
 DIRECT ACTING REQUIRING NO MORE THAN ONE OPERATION.
 DOUBLE CYLINDER DEAD BOLTS, REQUIRING A KEY FOR
 OPERATION ON BOTH SIDES, ARE PROHIBITED ON REQUIRED
 MEANS OF EGRESS DOORS UNLESS THE LOCKING DEVICE IS
 PROVIDED WITH A KEY WHICH CANNOT BE REMOVED WHEN THE
 DOOR IS LOCKED FROM THE INSIDE. ONLY ONE LOCKING OR
 LATCHING DEVICE SHALL BE PERMITTED ON A DOOR OR ON ONE
 LEAF OF A PAIR OF DOORS.
 SEE EXECPTION #2 FOR STORAGE OR EQUIPMENT ROOMS.
  
 1008.1.8.3 LOCKS AND LATCHES (3). WHERE EGRESS DOORS
 ARE USED IN PAIRS, APPROVED AUTOMATIC FLUSH BOLTS SHALL
 BE PERMITTED TO BE USED, PROVIDED THAT THE DOOR LEAF
 HAVING THE AUTOMATIC FLUSH BOLTS HAS NO DOORKNOB OR
 SURFACE-MOUNTED HARDWARE.
  
 8) THE NEW BACK EXIT DOOR MISSING THE MANEUVERING
 CLEARANCES REQUIRED BY THE NEW STORAGE ROOM 2010 FBC
 ACCESSIBILITY 404.2.4 & FIGURE 404.2.4.1 (C).
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  