Plan Review Notes
Plan Review Notes For Permit 12040429
Permit Number 12040429
Review Stop E
Sequence Number 1
Notes
Date Text
2012-05-01 14:52:5312040429
 7587 S. DIXIE HWY
 INTERIOR IMPROVEMENTS
  
  
 PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING
 COMPLIANCE WITH THE 2010 FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 505.5.3
 ALL RECEPTACLES LOCATED WITH IN SIX FEET OF A SINK MUST
 BE GFCI PROTECTED. NEC 210.8
 VERIFY COMPLIANCE WITH LIGHTING REQUIREMENTS FOR CLASS
 ROOMS. 2010 FBC 443.3.7
  
 NOTE:
 SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE
 ALARM SYSTEM, VOICE AND DATA.
  
  
 ROBERT LECKY, CBO
 ELECTRICAL PLANS EXAMINER