| 2012-05-04 15:25:12 | BUILDING PLAN REVIEW |
| | PERMIT: 12040429 |
| | ADD: 7587-7599 S DIXIE HWY |
| | CONT: CANDAS CONSTRUCTION |
| | TEL: (954)321-3442 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET LSP-1 INDICATE TWO AREAS THAT ARE CONSIDERED |
| | ASSMEBLY OCCUPANCIES THE SALON AREA AND CLASSROOMS 134 |
| | & 135. THE DESIGNER OF RECORD HAS NOT DECLARED IF THE |
| | INTENT IS SEPERATED OCCUPNCIES OR NON-SEPERATED |
| | OCCUPANCIES PER 2010 FBC-B: |
| | 508.2.5.1 FIRE-RESISTANCE-RATED SEPERATION. |
| | 508.2.5.2 NONFIRE-RESISTANCE-RATED SEPERATION AND |
| | PROTECTION. |
| | DEPENDING ON THE OUTCOME OF THIS SITUATION MORE |
| | COMMENTS MAY OCCUR WITH OPENING PROTECTION REQUIREMENTS |
| | TABLE 715.4. |
| | |
| | 2) LSP-1 ROOM # 133 LABELED A UTILITY ROOM THE USAGE |
| | WITH A WASHER AND DRYER IS MORE IN LINE WITH LAUNDRY |
| | PLEASE SEE THE REQUIREMENTS 1 HOUR PROTECTED OR FIRE |
| | SPRINKLERED, PLANS INDICATE THE BUILDING BEING FIRE |
| | SPRINKLERED. MAY OR MAYNOT REQUIRE SEPERATION PLEASE |
| | REVIEW 508.2.5.2 , 508.2.5.3 AND 508.3 NONSEPERATED |
| | OCCUPANCIES. |
| | |
| | 3) RESTROOMS AND VICHY ROOM INDICATE THE USE OF TILE |
| | WALLS BUT THE PLANS LACK THE TYPE OF BACKING TO BE USED |
| | IN THE INSTALATION. PLEASE REVIEW SECTION : |
| | 2010 FBC-B 2509.2 BASE FOR TILE. CEMENT, FIBER-CEMENT |
| | OR GLASS MAT GYPSUM BACKERS IN COMPLIANCE WITH ASTM C |
| | 1178, C 1288 OR C 1325 AND INSTALLED IN ACCORDANCE WITH |
| | MANUFACTURER RECOMMENDATIONS SHALL BE USED AS A BASE |
| | FOR WALL TILE IN TUB AND SHOWER AREAS AND WALL AND |
| | CEILING PANELS IN SHOWER AREAS. WATER-RESISTANT GYPSUM |
| | BACKING BOARD SHALL BE USED AS A BASE FOR TILE IN WATER |
| | CLOSET COMPARTMENT WALLS WHEN INSTALLED IN ACCORDANCE |
| | WITH GA-216 OR ASTM C 840 AND MANUFACTURER |
| | RECOMMENDATIONS. REGULAR GYPSUM WALLBOARD IS PERMITTED |
| | UNDER TILE OR WALL PANELS IN OTHER WALL AND CEILING |
| | AREAS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM |
| | C 840. |
| | |
| | 4) SHEET A-3 PLEASE PROVIDE COMPLIANCE WITH SECTION |
| | 2010 ACCESSIBILITY CODE 803.1-5. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |