2012-04-25 11:21:17319 CLEMATIS STREET - #910
 PERMIT #12040421
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL
 DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE
 ALARM SYSTEM.
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER.
  
 NO FIRE ALARM NOTIFICATION APPLIANCES SHOWN.
  
 SHEET M-2 DOES NOT INDICATE ANY FIRE DAMPERS WHERE
 DUCTWORK IS PENETRATING FIRE RATED ASSEMBLIES. ALSO
 SHOWS EXISTING DUCTWORK ROUTED THROUGH A FIRE RATED
 STAIR ENCLOSURE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  