| 2012-04-25 11:21:17 | 319 CLEMATIS STREET - #910 |
| | PERMIT #12040421 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL |
| | DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE |
| | ALARM SYSTEM. |
| | |
| | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS |
| | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE |
| | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL |
| | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. |
| | |
| | EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | NO FIRE ALARM NOTIFICATION APPLIANCES SHOWN. |
| | |
| | SHEET M-2 DOES NOT INDICATE ANY FIRE DAMPERS WHERE |
| | DUCTWORK IS PENETRATING FIRE RATED ASSEMBLIES. ALSO |
| | SHOWS EXISTING DUCTWORK ROUTED THROUGH A FIRE RATED |
| | STAIR ENCLOSURE. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |