Plan Review Notes
Plan Review Notes For Permit 12040376
Permit Number 12040376
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-23 10:55:51BUILDING PLAN REVIEW
 PERMIT: 12040376
 ADD: 319 CLEMATIS ST # 1004
 CONT: CLAY KOHLMEYER
 TEL: (561)719-3429
  
 2010 FLORIDA BUILDING CODE W/
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) 2010 FL EXIST BLDG CODE. THE DESIGNER OF RECORD
 SHALL INDICATE TO WHICH METHOD OF COMPLIANCE THIS PLAN
 WAS DESIGNED. 2010 FL EXIST BLDG CODE 101.5.
  
 2) CS-1 PROJECT DETAILS INDICATE THIS BUILDING TO BE 10
 STORIES, TYPE I-B, SPRINKLERED AND UNPROTECTED!
 PLEASE REVIEW 2010 FBC-B TABLE 603 INTERIOR BEARING
 WALLS (INTERIOR COLUMNS) 3 HOURS SEE FOOTNOTE A
 ALLOWING A 1 HOUR REDUCTION FOR SUPPORTING 1 STORY OR
 ROOF ABOVE.
 PLANS (COVERSHEET) DO NOT INDICATE PROTECTION OF
 STRUCTURAL ELEMENTS NOR DOES LS-1 OR A-1.0 FOR THE NEW
 PARTITIONS THAT SURROUND THE EXISTING COLUMNS. SHEET
 A-3.0 DOES INDICATE WALL TYPES BUT THE WALLS
 SURROUNDING THE COLUMNS ARE NOT IDENTIFIED WITH ANY
 WALL IDENTIFICATION TAGS.
  
 3) SHEET A-1.0 INDICATES TENANT SEPERATION WALLS TO BE
 RATED THE THE WALL LEGEND BUT WALL TAGS ARE NOT
 PROVIDED IDENTIFYING WHICH WALL APPLICATION LOCATED ON
 SHEET A-3.0 WILL BE CONSTRUCTED? 106.3.5.1.1(4) *. FIRE
 RESISTANT SEPERATIONS.
  
 4) PLANS DO NOT PROVIDE COMPLIANCE WITH 2010 FBC-B
 712.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 5) SHEET A-1.0 DOES INDICATE A RECEPTIONIST, NO PLANS
 WERE SUBMITTED INDICATING THE TYPE OF DESK/ COUNTER TO
 BE LOCATED AT THIS LOCATION. COMPLIANCE WITH 2010 FBC-B
 -ACCESSIBILITY CODE 904.4 SERVICE COUNTERS CAN NOT BE
 DETERMINED DURING THIS REVIEW OR IF THEY ARE REQUIRED?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715