| 2012-04-19 16:23:25 | FAILED | | | | | | 1) PROVIDE 2 COPIES OF A RECENT SURVEY, LESS THAN ONE | | | YEAR OLD, SHOWING ALL THE FEATURES ON THE PROPERTY. | | | | | | 2) THE STRUCTURAL/FLOOR PLANS SHOW ONE ADDITION ON THE | | | WEST SIDE OF THE EXISTING HOUSE, WHILE THE MARKED UP | | | OLD SURVEY SHOWS TWO ADDITIONS ON THE EAST SIDE OF THE | | | EXISTING HOUSE. PROVIDE ACCURATE INFORMATION, TO | | | INCLUDE ACCURATE SETBACK DIMENSIONS, AS TO THE LOCATION | | | AND SIZE OF THE ADDITION ON THE SITE PLAN. | | | | | | 3) THE PROPOSED ROOF AND SUPPORT POSTS OVER THE PATIO | | | ON THE NORTH SIDE OF THE HOUSE ENCROACH INTO THE | | | REQUIRED 10 FOOT REAR SETBACK. THE PLANS SHALL CLEARLY | | | SHOW NO ENCROACHMENT. | | | | | | 4) SHOW THE LOCATION, WITH SETBACK DIMENSIONS, OF NEW | | | OR RELOCATED A/C EQUIPMENT ON THE SITE PLAN. | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED BASED ON THE | | | PROVISION OF ACCURATE INFORMATION. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. |
|