| Notes |
| Date |
Text |
| 2012-05-14 14:31:12 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO SETS OF MECHANICAL PLANS WITH THE NAME | | | AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. | | | SPECIFY THE SIZE AND LOCATION OF SUPPLY AND RETURN | | | DUCTS. SPECIFY THE GRILL SIZES AND THE CFMS AT EACH | | | DROP. CITY AMENDMENTS 107.3.5.3 | | | | | | 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE NEW | | | ADDITION AS REQUIRED BY 2010 FBC ENERGY CONSERVATION | | | SECTION 401.2. | | | | | | 3) IF NEW EQUIPMENT IS BEING INSTALLED, SUBMIT TWO | | | COPIES OF THE EQUIPMENT SIZING CALCULATIONS AND PROVIDE | | | AN EQUIPMENT SCHEDULE ON THE PLANS. FBC 1401.3 | | | | | | 4) PLANS SHOWN NEW A/C EQUIPMENT LOCATED IN THE ATTIC. | | | SPECIFY THE SIZE AND LOCATION OF ATTIC ACCESS AND SHOW | | | COMPLIANCE WITH FBCR M1305.1.3. | | | | | | 5) SHOW THE LOCATION OF THE NEW A/C CONDENSING UNIT ON | | | THE PLANS. | | | | | | 6) SHOW COMPLIANCE WITH FBC M 1507.1 FOR MECHANICAL | | | BATHROOM VENTILATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|