2012-05-14 14:31:122010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO SETS OF MECHANICAL PLANS WITH THE NAME
 AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN.
 SPECIFY THE SIZE AND LOCATION OF SUPPLY AND RETURN
 DUCTS. SPECIFY THE GRILL SIZES AND THE CFMS AT EACH
 DROP. CITY AMENDMENTS 107.3.5.3
  
 2) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE NEW
 ADDITION AS REQUIRED BY 2010 FBC ENERGY CONSERVATION
 SECTION 401.2.
  
 3) IF NEW EQUIPMENT IS BEING INSTALLED, SUBMIT TWO
 COPIES OF THE EQUIPMENT SIZING CALCULATIONS AND PROVIDE
 AN EQUIPMENT SCHEDULE ON THE PLANS. FBC 1401.3
  
 4) PLANS SHOWN NEW A/C EQUIPMENT LOCATED IN THE ATTIC.
 SPECIFY THE SIZE AND LOCATION OF ATTIC ACCESS AND SHOW
 COMPLIANCE WITH FBCR M1305.1.3.
  
 5) SHOW THE LOCATION OF THE NEW A/C CONDENSING UNIT ON
 THE PLANS.
  
 6) SHOW COMPLIANCE WITH FBC M 1507.1 FOR MECHANICAL
 BATHROOM VENTILATION.
  