| 2012-05-14 14:53:55 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE 2010 FLORIDA BUILDING CODE BECAME EFFECTIVE ON |
| | MARCH 15, 2012 AND THE PERMIT WAS APPLIED FOR ON APRIL |
| | 13, 2012. THEREFORE, THE PLANS ARE REQUIRED TO BE |
| | DESIGNED TO COMPLY WITH THE 2010 FBC. PLEASE REVISE THE |
| | PLANS TO REFERENCE THE 2010 FBC. FS |
| | |
| | 2) UNDER THE 2010 FBC, THE WIND SPEED IS 170 MPH. |
| | PLEASE REVISE. FBC R301.2.1 |
| | |
| | 3) THE LOCATION OF THE ADDITION THAT WAS DRAWN ON THE |
| | SURVEY DOES NOT MATCH THE LOCATION SHOWN ON THE PLANS. |
| | PLEASE PROVIDE TWO COPIES OF AN ACCURATE SITE PLAN |
| | INDICATING THE DISTANCES FROM THE NEW ADDITION TO THE |
| | PROPERTY LINES. FBC 302.1 |
| | |
| | 4) SUBMIT TWO COPIES OF A SITE DRAINAGE PLAN SHOWING |
| | COMPLIANCE WITH FBC R401.3. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R318.1 FOR TERMITE |
| | PROTECTION. |
| | |
| | 6) PROVIDE TWO SETS OF FLOOR PLANS SHOWING ALL ROOM |
| | DIMENSIONS, WINDOW AND DOOR SIZES, ETC. DRAWN TO SCALE |
| | (MINIMUM 1/8" SCALE) WITH THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN. CITY AMENDMENTS |
| | 107.2.1 AND 107.2.1.4 |
| | |
| | 7) SUBMIT ENERGY CALCULATIONS SHOWING COMPLIANCE WITH |
| | FBC ENERGY CONSERVATION SECTION 401.2. |
| | |
| | 8) SPECIFY THE CEILING INSULATION ON THE PLANS. FBC |
| | ENERGY CONSERVATION SECTION 401 |
| | |
| | 9) SHEET S-2 SPECIFIES A 12" DEEP MONOLITHIC |
| | FOUNDATION. FBC R403.1.4 REQUIRES FOOTINGS TO BE A |
| | MINIMUM OF 12" BELOW GRADE AND R404.1.6 REQUIRES |
| | CONCRETE FOUNDATIONS TO EXTEND 6" ABOVE FINISHED GRADE. |
| | THEREFORE, AN 18" THICKENED EDGE IS REQUIRED. |
| | |
| | 10) SHOW COMPLIANCE WITH ASTM C 1063 WHICH REQUIRES A |
| | FOUNDATION WEEP SCREED FOR EXTERIOR STUCCO WALLS AT THE |
| | BOTTOM OF ALL FRAMED EXTERIOR WALLS, BELOW THE FLOOR |
| | LINE. |
| | |
| | 11) PROVIDE FINISHED EXTERIOR ELEVATIONS ON THE PLANS |
| | SHOWING DIMENSIONS AND DRAWN TO SCALE. CITY AMENDMENTS |
| | 107.2..1 AND 107.2.1.4 |
| | |
| | 12) CLARIFY HOW THE EXTERIOR WALL WILL BE FINISHED TO |
| | PREVENT WATER INTRUSION WHERE THE PATIO RAFTERS |
| | PENETRATE INTO THE NORTH WALL. FBC R703.1 |
| | |
| | 13) SPECIFY THE ROOF PITCH ON THE PLANS. FBC R905.2.2 |
| | |
| | 14) SPECIFY THE SOFFIT COVERING MATERIAL ON THE PLANS. |
| | FBC R703.1.2 |
| | |
| | 15) SPECIFY THE INTERIOR CEILING FINISH MATERIAL ON THE |
| | PLANS. FBC R805 |
| | |
| | 16) SPECIFY THE LOCATION AND SIZE OF THE ATTIC ACCESS |
| | FOR THE NEW A/C AIR HANDLER THAT IS LOCATED IN THE |
| | ATTIC. FBC R807.1 |
| | |
| | 17) CLARIFY THE NOTE ON SHEET S-3 THAT STATES 1 X 6 |
| | COLLAR TIES WHERE FEASIBLE. |
| | |
| | 18) SHOW COMPLIANCE WITH FBC R806 FOR ROOF VENTILATION. |
| | |
| | 19) SHOW COMPLIANCE WITH FBC R803.2.3.1 FOR ROOF |
| | SHEATHING FASTENING REQUIREMENTS. |
| | |
| | 20) THE PLANS APPEAR TO INDICATE THAT THE ADDITION HAS |
| | A CATHEDRAL CEILING. PLEASE SHOW HOW THE LATERAL WIND |
| | LOADS WILL BE ADDRESSED WITHOUT A CEILING DIAPHRAGM. |
| | PROVIDE CALCULATIONS. CITY AMENDMENTS 107.107.2.1.3 |
| | |
| | 21) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOORS, WINDOWS AND ROOFING COVERING MATERIAL |
| | AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 22) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PER |
| | CITY AMENDMENTS 107.3.4.1. |
| | |
| | 24) SHOW COMPLIANCE WITH FBC R301.2.1.2 FOR PROTECTION |
| | OF OPENINGS FROM WINDBORNE DEBRIS. |
| | |
| | 25) NOTE: IN ORDER TO SPEED PLAN REVIEW TIME, PLEASE |
| | SUBMIT A RESPONSE LETTER INDICATING HOW EACH OF THE |
| | REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |