Plan Review Notes
Plan Review Notes For Permit 12040363
Permit Number 12040363
Review Stop B
Sequence Number 1
Notes
Date Text
2012-05-14 14:53:552010 FBC
  
 DENIED BY BUILDING
  
 1) THE 2010 FLORIDA BUILDING CODE BECAME EFFECTIVE ON
 MARCH 15, 2012 AND THE PERMIT WAS APPLIED FOR ON APRIL
 13, 2012. THEREFORE, THE PLANS ARE REQUIRED TO BE
 DESIGNED TO COMPLY WITH THE 2010 FBC. PLEASE REVISE THE
 PLANS TO REFERENCE THE 2010 FBC. FS
  
 2) UNDER THE 2010 FBC, THE WIND SPEED IS 170 MPH.
 PLEASE REVISE. FBC R301.2.1
  
 3) THE LOCATION OF THE ADDITION THAT WAS DRAWN ON THE
 SURVEY DOES NOT MATCH THE LOCATION SHOWN ON THE PLANS.
 PLEASE PROVIDE TWO COPIES OF AN ACCURATE SITE PLAN
 INDICATING THE DISTANCES FROM THE NEW ADDITION TO THE
 PROPERTY LINES. FBC 302.1
  
 4) SUBMIT TWO COPIES OF A SITE DRAINAGE PLAN SHOWING
 COMPLIANCE WITH FBC R401.3.
  
 5) SHOW COMPLIANCE WITH FBC R318.1 FOR TERMITE
 PROTECTION.
  
 6) PROVIDE TWO SETS OF FLOOR PLANS SHOWING ALL ROOM
 DIMENSIONS, WINDOW AND DOOR SIZES, ETC. DRAWN TO SCALE
 (MINIMUM 1/8" SCALE) WITH THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. CITY AMENDMENTS
 107.2.1 AND 107.2.1.4
  
 7) SUBMIT ENERGY CALCULATIONS SHOWING COMPLIANCE WITH
 FBC ENERGY CONSERVATION SECTION 401.2.
  
 8) SPECIFY THE CEILING INSULATION ON THE PLANS. FBC
 ENERGY CONSERVATION SECTION 401
  
 9) SHEET S-2 SPECIFIES A 12" DEEP MONOLITHIC
 FOUNDATION. FBC R403.1.4 REQUIRES FOOTINGS TO BE A
 MINIMUM OF 12" BELOW GRADE AND R404.1.6 REQUIRES
 CONCRETE FOUNDATIONS TO EXTEND 6" ABOVE FINISHED GRADE.
 THEREFORE, AN 18" THICKENED EDGE IS REQUIRED.
  
 10) SHOW COMPLIANCE WITH ASTM C 1063 WHICH REQUIRES A
 FOUNDATION WEEP SCREED FOR EXTERIOR STUCCO WALLS AT THE
 BOTTOM OF ALL FRAMED EXTERIOR WALLS, BELOW THE FLOOR
 LINE.
  
 11) PROVIDE FINISHED EXTERIOR ELEVATIONS ON THE PLANS
 SHOWING DIMENSIONS AND DRAWN TO SCALE. CITY AMENDMENTS
 107.2..1 AND 107.2.1.4
  
 12) CLARIFY HOW THE EXTERIOR WALL WILL BE FINISHED TO
 PREVENT WATER INTRUSION WHERE THE PATIO RAFTERS
 PENETRATE INTO THE NORTH WALL. FBC R703.1
  
 13) SPECIFY THE ROOF PITCH ON THE PLANS. FBC R905.2.2
  
 14) SPECIFY THE SOFFIT COVERING MATERIAL ON THE PLANS.
 FBC R703.1.2
  
 15) SPECIFY THE INTERIOR CEILING FINISH MATERIAL ON THE
 PLANS. FBC R805
  
 16) SPECIFY THE LOCATION AND SIZE OF THE ATTIC ACCESS
 FOR THE NEW A/C AIR HANDLER THAT IS LOCATED IN THE
 ATTIC. FBC R807.1
  
 17) CLARIFY THE NOTE ON SHEET S-3 THAT STATES 1 X 6
 COLLAR TIES WHERE FEASIBLE.
  
 18) SHOW COMPLIANCE WITH FBC R806 FOR ROOF VENTILATION.
  
 19) SHOW COMPLIANCE WITH FBC R803.2.3.1 FOR ROOF
 SHEATHING FASTENING REQUIREMENTS.
  
 20) THE PLANS APPEAR TO INDICATE THAT THE ADDITION HAS
 A CATHEDRAL CEILING. PLEASE SHOW HOW THE LATERAL WIND
 LOADS WILL BE ADDRESSED WITHOUT A CEILING DIAPHRAGM.
 PROVIDE CALCULATIONS. CITY AMENDMENTS 107.107.2.1.3
  
 21) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS, WINDOWS AND ROOFING COVERING MATERIAL
 AS REQUIRED BY DCA RULE 9N-3.
  
 22) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PER
 CITY AMENDMENTS 107.3.4.1.
  
 24) SHOW COMPLIANCE WITH FBC R301.2.1.2 FOR PROTECTION
 OF OPENINGS FROM WINDBORNE DEBRIS.
  
 25) NOTE: IN ORDER TO SPEED PLAN REVIEW TIME, PLEASE
 SUBMIT A RESPONSE LETTER INDICATING HOW EACH OF THE
 REVIEW COMMENTS HAS BEEN ADDRESSED.
  