| 2012-05-18 15:36:16 | BUILDING PLAN REVIEW |
| | PERMIT: 12040343 |
| | ADD: 1641 WORTHINGTON # 120 |
| | CONT: DPR CONSTRUCTION |
| | TEL: (561)632-4028 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) COMPLIED. 5/28/2012 PLEASE SEE 2010 FBC-B 1014.3(2) |
| | IS FOR NON-SPRIKLERED BUILDINGS. |
| | 2) SHEET A-1 THIS IS A 4 STORY BUILDING WHICH WILL |
| | REQUIRE THE VERTICAL STAIRS TO HAVE A 2 HR WALL 2010 |
| | FBC-B 1022.1. THE CONTINUATION OF THIS EXIT BEING A |
| | EXIT PASSAGE WAY MUST HAVE THE SAME FIRE RATING PER |
| | 2010 FBC-B 1023.3. WALL TAG MARKER INDICATES THE EXIT |
| | PASSAGE WALL TO BE A ONE OUR RATED WALL. |
| | |
| | 3) SHEET A-1 THE COMMON TENANT WALL WITH THE EXIT |
| | ACCESS CORRIDOR IS INDICATED WITH A WALL TAG # 4 BUT |
| | THIS DESIGNATION ISN'T LOCATED IN THE WALL LEGEND. |
| | 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | 2010 FBC-B 709.1(6) TENANT SEPERATION WALLS. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |