| Plan Review Notes For Permit 12040320 |
| Permit Number |
12040320 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-20 14:27:27 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | | | | 1. DESIGN PRESSURES APPEAR TOO LOW. EXPOSURE C, 15 MRH, | | | 10 SF OPENING (WORST CASE) ZONE 4, DESIGN PRESSURES | | | SHOULD BE +37.9 / -41.1; -36.7 PROPOSED. IT IS NOT | | | CLEAR HOW YOU HAVE DETERMINED DESIGN PRESSURES, SEE FBC | | | R 301.2(2). | | | | | | NOTE THAT THE LARGER OPENINGS HAVE HIGHER DESIGN | | | PRESSURES, WHICH IS NOT CORRECT. PLEASE FEEL FREE TO | | | CONTACT ME IF YOU WISH TO DISCUSS METHODS OF | | | DETERMINING DESIGN PRESSURE REQUIREMENTS. | | | |
|