2012-04-12 11:24:14560 OKEECHOBEE BOULEVARD
 PERMIT #12040290
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO*****
  
 **THE PERMIT APPLICATION WAS SUBMITTED 04/11/12;
 HOWEVER, THIS WRITER INSPECTED AND OBSERVED (04/11/12)
 THAT THE TENTS AND PLATFORMS WERE ALREADY INSTALLED AT
 THIS LOCATION PRIOR TO OBTAINING CITY PLAN REVIEWS AND
 PERMITS.**
  
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL
 DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET.
  
 TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM
 BUILDING STRUCTURES. NOTE: TENTS WERE ALREADY INSTALLED
 WITH 0 FEET BETWEEN TENT AND BUILDING STRUCTURE.
  
 TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE,
 OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS
 ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET.
  
 POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS
 LOCATIONS.
  
 PROVIDE EXIT SIGN ON BOTH EXTERIOR METAL GATES.
  
 PROVIDE HANDRAILS ON BOTH SIDES OF STEPS USED FOR
 ACCESS TO THE 30" TALL PLATFORM.
  
 SUBMIT INFORMATION (HEIGHT, WEIGHT LOADS,
 ACCESSIBILITY) TO BUILDING DEPT FOR REVIEW.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  