| 2012-04-12 11:24:14 | 560 OKEECHOBEE BOULEVARD | | | PERMIT #12040290 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | *****PROVISO***** | | | | | | **THE PERMIT APPLICATION WAS SUBMITTED 04/11/12; | | | HOWEVER, THIS WRITER INSPECTED AND OBSERVED (04/11/12) | | | THAT THE TENTS AND PLATFORMS WERE ALREADY INSTALLED AT | | | THIS LOCATION PRIOR TO OBTAINING CITY PLAN REVIEWS AND | | | PERMITS.** | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | TENTS SHALL BE LOCATED AT LEAST 10 FEET AWAY FROM | | | BUILDING STRUCTURES. NOTE: TENTS WERE ALREADY INSTALLED | | | WITH 0 FEET BETWEEN TENT AND BUILDING STRUCTURE. | | | | | | TENT SHALL BE OF THE OPEN AREA/NO SIDEWALL TYPE, | | | OTHERWISE EMERGENCY LIGHTING AND ILLUMINATED EXIT SIGNS | | | ARE REQUIRED FOR TENTS EXCEEDING 1,200 SQUARE FEET. | | | | | | POST WEATHERPROOF NO SMOKING SIGNS IN CONSPICUOUS | | | LOCATIONS. | | | | | | PROVIDE EXIT SIGN ON BOTH EXTERIOR METAL GATES. | | | | | | PROVIDE HANDRAILS ON BOTH SIDES OF STEPS USED FOR | | | ACCESS TO THE 30" TALL PLATFORM. | | | | | | SUBMIT INFORMATION (HEIGHT, WEIGHT LOADS, | | | ACCESSIBILITY) TO BUILDING DEPT FOR REVIEW. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|