| 2012-11-13 14:33:58 | RESIDENTIAL (R3) ADDITION THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | CODE: 2010 FBC. |
| | |
| | 1- SOIL IN THIS AREA IS QUESTIONABLE. PROVIDE SOIL TEST |
| | REPORT AS REQUIRED BY SEC. R401.4 OF 2010 |
| | FBC-RESIDENTIAL. (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 2- ENGINEER REMOVED NOTE REGARDING THE SOIL BEARING |
| | CAPACITY USED FOR THE DESIGN. ENGINEER TO SPECIFY SOIL |
| | BEARING CAPACITY FOR WHICH STRUCTURE WAS DESIGNED. |
| | ENGINEER TO READ SOIL TEST REPORT TO VERIFY IF PROPOSED |
| | FOOTING DESIGN IS ADEQUATE BASED ON THE TYPE AND |
| | BEARING CAPACITY OF THE SOIL. SEC. R301.1 OF 2010 FBC. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ACCORDION SHUTTERS. NOA 07-0828.12 SUBMITTED EXPIRED |
| | ON 10/29/12. NEED CURRENT NOA. |
| | |
| | B) THERE ARE DIFFERENT PRODUCT APPROVALS SUBMITTED FOR |
| | THE EXTERIOR DOORS. CLARIFY WHICH ONE IS GOING TO BE |
| | USED. CHECK THE DESIGN PRESSURES WITH DESIGN PRESSURES |
| | SPECIFIED BY THE ENGINEER. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | (REPEAT COMMENT. NOT ADDRESSED). |
| | |
| | 5- PROVIDE COMPLETE INSTALLATION FOR THE INSTALLATION |
| | OF ACCORDION SHUTTERS SUBMITTED. SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 6- PROVIDE DETAILS/SPECIFICATIONS FOR DOOR STRUCTURAL |
| | BUCK SIZE AS REQUIRED BY THE DOOR PRODUCT APPROVAL |
| | SUBMITTED. SPECIFY ALL FASTENERS (SIZE AND SPACING). |
| | STRUCTURAL BUCK TO COMPLY WITH SEC. R612.10.2.1 OF 2010 |
| | FBC-RESIDENTIAL. (REPEAT COMMENT. BUCK SIZE SPECIFIED |
| | DON'T COMPLY WITH PRODUCT APPROVAL SUBMITTED. AND, |
| | FASTENER SPACING WAS NOT SPECIFIED. |
| | |
| | 7- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT |
| | FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT |
| | FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | (REPEAT COMMENT). |
| | |
| | |
| | ****NOTE: ONE SET OF PLANS WAS TAKEN OUT AND WAS NOT |
| | RETURNED. MISSING THE A/C, ELECTRICAL AND PLUMBING |
| | PLANS. WE HAVE ONLY ONE COPY. NEED TO COPIES. |
| | |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |