| 2012-08-07 15:21:25 | RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- SOIL IN THIS AREA IS QUESTIONABLE. PROVIDE SOIL TEST |
| | REPORT AS REQUIRED BY SEC. R401.4 OF 2010 |
| | FBC-RESIDENTIAL. |
| | NOTE: ENGINEER REMOVED NOTE REGARDING THE SOIL BEARING |
| | CAPACITY USED FOR THE DESIGN. ENGINEER TO SPECIFY SOIL |
| | BEARING CAPACITY FOR WHICH STRUCTURE WAS DESIGNED. |
| | ENGINEER TO READ SOIL TEST REPORT TO VERIFY IF PROPOSED |
| | FOOTING DESIGN IS ADEQUATE BASED ON THE TYPE AND |
| | BEARING CAPACITY OF THE SOIL. |
| | |
| | 2- REVISE THE ENERGY CALCULATIONS TO MATCH PLANS. |
| | A) PLANS SHOW VENTED ATTIC. |
| | B) ROOF MATERIAL IS SHINGLES NOT CONCRETE TILE. |
| | C) CEILING TYPE IS NOT CATHEDRAL/SINGLE ASSEMBLY. SEE |
| | PLANS AND REVISE. |
| | D) KITCHEN IS NOT INCLUDED IN THE ADDITION. SEE PLANS. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SINGLE HUNG WINDOWS. NOA 06-0407.02 SUBMITTED |
| | EXPIRED ON AUGUST 10, 2011. PROVIDE TWO NEW COPIES. |
| | |
| | B) SHUTTERS IF NOT USING IMPACT WINDOWS. AND, PROVIDE |
| | COMPLETE INSTALLATION SCHEDULE. PROVIDE 2 COPIES. |
| | |
| | 4- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | ALL PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 109.3 CITY AMENDMENTS. VALUATION WAS UPDATED, |
| | OWES $1432.91. |
| | |
| | 6- PROVIDE DETAILS/SPECIFICATIONS FOR DOOR STRUCTURAL |
| | BUCK SIZE AS REQUIRED BY THE DOOR PRODUCT APPROVAL |
| | SUBMITTED. SPECIFY ALL FASTENERS. STRUCTURAL BUCK TO |
| | COMPLY WITH SEC. R612.10.2.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 7- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY BUILDING (2300 N. JOG RD.) TO VERIFY IF IMPACT |
| | FEES ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT |
| | FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE. |
| | |