| 2012-05-15 10:06:58 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | |
| | 1- AFTER PLANS ARE REVISED, PLEASE BRING THEM TO PALM |
| | BEACH COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES |
| | ARE DUE. THEN, BRING BACK STAMPED PLANS AND COPY OF |
| | PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. 401 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 3- ENGINEER NEEDS TO UPDATE ALL THE PLANS. CURRENT CODE |
| | IN EFFECT IS THE 2010 FLORIDA RESIDENTIAL CODE AND THE |
| | 2010 FBC. REVISE ALL THE DESIGN INFORMATION |
| | ACCORDINGLY. UPDATE IN ALL PLANS ALL THE INFORMATION |
| | THAT REFERENCES THE 2007 FBC AND THE ASCE 7-05 AND |
| | REFERENCE CORRECT CURRENT SECTION. |
| | |
| | 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SINGLE HUNG WINDOWS SPECIFIED ON PLANS. NOA |
| | 09-0316.10 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. |
| | PLEASE VISIT THE MIAMI-DADE WEBSITE AND DOWNLOAD |
| | CURRENT NOA. |
| | |
| | B) ROOF SHINGLES. PROVIDE 2 COPIES. ONLY ONE WAS |
| | SUBMITTED. |
| | |
| | C) EXTERIOR DOOR. PROVIDE 2 COPIES. ONLY ONE WAS |
| | SUBMITTED. |
| | |
| | D) HURRICANE SHUTTERS FOR SINGLE HUNG WINDOWS SINCE |
| | WINDOWS HAVE NO IMPACT GLASS. AND, PROVIDE COMPLETE |
| | INSTALLATION SCHEDULE SHOWING SPECIFIC MOUNTING |
| | CONDITIONS AND ANCHOR TYPE AND SPACING TO BE USED. |
| | |
| | E) ALL USP STRUCTURAL CONNECTORS SPECIFIED BY THE |
| | ENGINEER ON PLANS AND DETAILS. PROVIDE ONLY THE PRODUCT |
| | APPROVAL COVER PAGE AND PAGE SHOWING THE STRUCTURAL |
| | CONNECTOR ONLY. THIS APPLIES TO STRUCTURAL CONNECTORS |
| | ONLY. |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS TO FBC. |
| | |
| | 6- ENGINEER SPECIFIED ON WALL SECTION ON SHEET A-1 AND |
| | ON SHEET A-3 THAT THE SOIL WAS OBSERVED TO BE SAND AND |
| | ROCK. THIS IS NOT THE TYPE OF SOIL ON THIS AREA. |
| | PROVIDE SOIL TEST REPORT AS REQUIRED BY SEC. R401.4 AND |
| | ENGINEER TO REVISE SPECS AS REQUIRED BASED ON THE SOIL |
| | TEST REPORT FINDINGS. |
| | |
| | 7- WALL SECTIONS SPECIFY ROOF PITCH OF 3/12. ENGINEER |
| | NEEDS TO SPECIFY 2 LAYERS OF UNDERLAYMENT AS REQUIRED |
| | BY SEC. R905.2.2. |
| | |
| | 8- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND |
| | DESIGN PROFESSIONAL FEES. SEC. 109.3 OF CITY AMENDMENTS |
| | TO FBC. VALUATION WAS UPDATED. OWES $1432.91. |
| | |
| | 9- WALL SECTION ON SHEET A-3 SHOWS THAT EXISTING |
| | TRUSSES ARE TO BE CUT TO RECEIVE NEW WALL. ENGINEER TO |
| | PROVIDE SPECIFICATIONS SHOWING HOW THE EXISTING TRUSSES |
| | ARE TO BE REINFORCED SO THE STRUCTURAL STABILITY IS NOT |
| | AFFECTED. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. |
| | |
| | 10- PROVIDE DETAILS/SPECIFICATIONS FOR DOORS AND |
| | WINDOWS BUCKS AS REQUIRED BY SEC. R612.10.2.1. |
| | |
| | 11-WALL SECTION ON SHEET A-1: |
| | A) FOOTING NEEDS TO BE MIN. 12" BELOW GRADE. SEC. |
| | R403.1.4. REVISE AS REQUIRED. |
| | |
| | B) SPECIFY ROOF EDGE WIDTH. 4'-0" WIDE MIN. AS REQUIRED |
| | BY FIGURE R301.2(7). |
| | |
| | 12- DOOR SCHEDULE ON SHEET A-1 IS MISSING DOOR #3 FOR |
| | NEW BEDROOM. REVISE AS REQUIRED. |
| | |
| | 13- SHEET A-2: |
| | A) FOUNDATION PLAN IS MISSING THE SPECIFICATION FOR THE |
| | WATER VAPOR BARRIER AS REQUIRED BY SEC. R506.2.3. |
| | |
| | B) ROOFING LOADS. SPECIFY ALL THE LIVE, DEAD AND WIND |
| | LOADS AS REQUIRED BY SEC. R301.1, TABLE R301.2(2) AND |
| | TABLE R301.5. AND CLEARLY IDENTIFY ALL ROOF ZONES AND |
| | WALL ZONES. |
| | |
| | C) UPDATE THE WIND CODE EDITION AND THE SECTIONS |
| | REFERENCED ON ON THE FOOTING AND TIE BEAM DETAIL. |
| | CURRENT CODE IW THE 2010 FLORIDA RESIDENTIAL CODE AND |
| | 2010 FBC. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |