| Plan Review Notes For Permit 12040255 |
| Permit Number |
12040255 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-24 11:36:25 | PROVISOS | | | | | | FIRE ALARM TO BE IN COMPLIANCE WITH NFPA 72 PER FBC | | | ACCESSIBILITY 215. PLEASE NOTE THE FOLLOWING: | | | | | | VISUAL STROBES NOT SHOWN IN ALL REQUIRED AREAS NFPA | | | 72-7.5.4.1. | | | | | | HORN/STROBE SHOWN IN RESTROOMS, APPEARS THAT SOUND | | | LEVEL WILL EXCEED 120 DBA, NFPA 72-7.4.1.2. | | | | | | BREAK ROOM DOOR, PULL SIDE, TO MEET 18" CLEARANCE FBC | | | ACCESSIBILITY 404.2.4. | | | |
|