| 2012-04-19 14:40:03 | RESIDENTIAL (R3) RENOVATIONS BUILDING REVIEW COMMENTS. |
| | 2010 EXISTING BUILDING CODE AND 2010 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | 1- ENERGY CALCULATIONS SUBMITTED: |
| | A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| | INCLUDING OWNER'S NAME, BUILDER'S NAME, ETC. |
| | B) REVISE ITEM #1. THIS IS NOT NEW CONSTRUCTION. THIS |
| | IS EXISTING HOUSE. |
| | C) REVISE ITEM #9(A). NOTES ON DRAWING A-1 SAYS "NEW |
| | R19 INSULATION ON EXTERIOR WALLS". REVISE AS REQUIRED. |
| | D) HOT WATER SYSTEM IS GAS NOT ELECTRIC. REVISE ITEM |
| | #14. |
| | E) A/C EQUIPMENT SIZING CALCULATIONS WERE DONE USING |
| | WORST CASE SCENARIO. THIS IS NOT ALLOWED. REVISE ITEMS |
| | #12 AND # 13 ONCE A/C EQUIPMENT SIZING CALCULATIONS ARE |
| | REVISED. |
| | F) REVISE TYPE OF DOOR SHOWN ON SHEET 3 OF 5. THERE ARE |
| | NOT WOOD DOORS. SEE SHEET A-1. |
| | G) THERE IS NOT GARAGE ON THIS BUILDING. REVISE SHEET 3 |
| | OF 4. |
| | H) MECHANICAL VENTILATION ON SHEET 4 OF 5. IT SAYS |
| | THERE IS NOT MECHANICAL VENTILATION. SEE A/C PLAN AND |
| | REVISE AS REQUIRED. THERE IS MECHANICAL VENTILATION FOR |
| | BATHROOM. |
| | |
| | 2- ARCHITECT TO SPECIFY CARBON MONOXIDE ALARMS AS |
| | REQUIRED BY SEC. R315. |
| | |
| | 3- ARCHITECT TO SPECIFY THE DESIGN PRESSURES FOR THE |
| | EXTERIOR DOORS AND WINDOWS. NOTE: ARCHITECT TO TAKE |
| | INTO CONSIDERATION THAT ACCORDING TO SEC. R301.2.1.4.3 |
| | THIS BUILDING IS LOCATED ON EXPOSURE "C". |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOF SHINGLES. NOA 11-0411.02 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. VISIT MIAMI-DADE WEBSITE AND |
| | DOWNLOAD CURRENT NOA. |
| | B) IN-SWING ENTRY DOOR AS SHOWN ON SHEET A-1. |
| | C) DOUBLE FRENCH DOORS AS SHOWN ON SHEET A-1. |
| | D) SINGLE HUNG WINDOWS. FLORIDA PRODUCT APPROVAL |
| | FL4065-R5 SUBMITTED IS FOR 2007 CODE VERSION. NEED ONE |
| | FOR CURRENT 2010 CODE VERSION. |
| | E) STORM PANELS. FLORIDA PRODUCT APPROVAL SUBMITTED IS |
| | FOR 2007 CODE VERSION. NEED ONE FOR CURRENT 2010 CODE |
| | VERSION. AND PROVIDE COMPLETE PRODUCT APPROVAL |
| | INCLUDING ALL THE SHUTTERS DRAWINGS. |
| | |
| | 5- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED |
| | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 6- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE STORM |
| | SHUTTERS INSTALLATION. CLEARLY SPECIFY SHUTTERS |
| | MOUNTING CONDITION (FOR EXAMPLE WALL MOUNTED, ETC) AND |
| | FASTENER TYPE AND SPACING AS REQUIRED BY PRODUCT |
| | APPROVAL SUBMITTED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.2.1.4.3. |
| | |
| | 7- CLARIFY IF WINDOWS ARE GOING TO BE REPLACED OR NOT. |
| | PLANS ONLY SPECIFY DOORS TO BE REPLACED, BUT WINDOW |
| | PRODUCT APPROVAL WAS SUBMITTED FOR REVIEW. |
| | |
| | 8- WINDOW ON BEDROOM #3 IS REQUIRED TO HAVE SAFETY |
| | GLASS. SEC. R308.4(2). |
| | |