| 2012-09-14 11:59:37 | RESIDENTIAL (R3) ADDITION THIRD BUILDING REVIEW |
| | CHECKLIST. |
| | 2010 FBC. |
| | |
| | 1- WALL SECTION: |
| | A) REVISE R-VALUE INSULATION SHOWN ON THE WALL SECTION |
| | TO MATCH INFORMATION GIVEN ON THE ENERGY CALCULATIONS. |
| | SEE TABLE 402A OF ENERGY CALCULATIONS SUBMITTED. REVISE |
| | AS REQUIRED. |
| | NOTE: CHECK VALUES GIVEN FOR INTERIOR OF WALL AND |
| | EXTERIOR OF WALL AND REVISE/COORDINATE WITH PLANS AS |
| | REQUIRED. |
| | |
| | B) R-30 BATT INSULATION DOESN'T FIT ON 2X8 ROOF |
| | RAFTERS. REVISE AS REQUIRED. NEED R-30 PER TABLE 402A |
| | OF ENERGY CALCULATIONS SUBMITTED. |
| | |
| | C) COORDINATE TYPE OF ROOFING SYSTEM TO BE INSTALLED |
| | WITH PRODUCT APPROVAL SUBMITTED. SEE ITEM 4(B) BELOW. |
| | REVISE AS REQUIRED. |
| | |
| | 2- FLAT ROOF NOA 11-0425.07 SUBMITTED: |
| | A) IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.2.1.4.3. |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR |
| | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS |
| | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA |
| | SUBMITTED. |
| | ***NOTE: IF DESIGN PRESSURES ON SELECTED ASSEMBLY ARE |
| | GOOD FOR THE PERIMETER AND CORNER AREAS, THEN |
| | ADDITIONAL RAS 117 CALCULATIONS ARE NOT REQUIRED. |
| | |
| | 3- NEED SEPARATE PERMITS FOR ELECTRICAL, MECHANICAL, |
| | PLUMBING, ROOFING. OWNER BUILDER CAN SIGN ON THE PERMIT |
| | APPLICATION FOR THESE SUBPERMITS OR CONTRACTORS MAY |
| | APPLY FOR THEIR OWN SUBPERMITS. INDICATE WHICH OPTION |
| | IS GOING TO BE. |
| | |