2012-09-14 11:59:37RESIDENTIAL (R3) ADDITION THIRD BUILDING REVIEW
 CHECKLIST.
 2010 FBC.
  
 1- WALL SECTION:
 A) REVISE R-VALUE INSULATION SHOWN ON THE WALL SECTION
 TO MATCH INFORMATION GIVEN ON THE ENERGY CALCULATIONS.
 SEE TABLE 402A OF ENERGY CALCULATIONS SUBMITTED. REVISE
 AS REQUIRED.
 NOTE: CHECK VALUES GIVEN FOR INTERIOR OF WALL AND
 EXTERIOR OF WALL AND REVISE/COORDINATE WITH PLANS AS
 REQUIRED.
  
 B) R-30 BATT INSULATION DOESN'T FIT ON 2X8 ROOF
 RAFTERS. REVISE AS REQUIRED. NEED R-30 PER TABLE 402A
 OF ENERGY CALCULATIONS SUBMITTED.
  
 C) COORDINATE TYPE OF ROOFING SYSTEM TO BE INSTALLED
 WITH PRODUCT APPROVAL SUBMITTED. SEE ITEM 4(B) BELOW.
 REVISE AS REQUIRED.
  
 2- FLAT ROOF NOA 11-0425.07 SUBMITTED:
 A) IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
 ***NOTE: IF DESIGN PRESSURES ON SELECTED ASSEMBLY ARE
 GOOD FOR THE PERIMETER AND CORNER AREAS, THEN
 ADDITIONAL RAS 117 CALCULATIONS ARE NOT REQUIRED.
  
 3- NEED SEPARATE PERMITS FOR ELECTRICAL, MECHANICAL,
 PLUMBING, ROOFING. OWNER BUILDER CAN SIGN ON THE PERMIT
 APPLICATION FOR THESE SUBPERMITS OR CONTRACTORS MAY
 APPLY FOR THEIR OWN SUBPERMITS. INDICATE WHICH OPTION
 IS GOING TO BE.
  