| Plan Review Notes For Permit 12040231 |
| Permit Number |
12040231 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-06-25 12:49:14 | RESIDENTIAL (R3) ADDITION MECHANICAL REVIEW SECOND | | | CHECKLIST. | | | 2010 FBC. | | | | | | 1- PLEASE PROVIDE SPECIFICATIONS ON PLANS SHOWING | | | COMPLIANCE WITH THE CLOTHES DRYER EXHAUST AS REQUIRED | | | BY SEC. M1502. NOT ADDRESSED. EXHAUST FAN NOT SHOWN. | | | | | | 2- PERSON RESPONSIBLE FOR THE DESIGN OF MECHANICAL | | | DRAWING M.1 NEEDS TO PROVIDE NAME AND SIGNATURE AS | | | REQUIRED BY SEC. 107.2.1 OF CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|