Plan Review Notes
Plan Review Notes For Permit 12040231
Permit Number 12040231
Review Stop B
Sequence Number 2
Notes
Date Text
2012-06-22 15:48:29RESIDENTIAL (R3) ADDITION SECOND BUILDING REVIEW
 CHECKLIST.
 2010 FBC.
  
 1- WALL SECTION:
 A) REVISE R-VALUE INSULATION SHOWN ON THE WALL SECTION
 TO MATCH INFORMATION GIVEN ON THE ENERGY CALCULATIONS.
 REQUIRED BY TABLE 402.1.1 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 B) R-30 BATT INSULATION DOESN'T FIT ON 2X8 ROOF
 RAFTERS. REVISE AS REQUIRED. NEED R-30 PER TABLE
 402.1.1.
  
 C) FOOTING SHALL BE 12" MIN. BELOW GRADE AS REQUIRED BY
 SEC. R403.1.4. REPEAT COMMENT. NOT ADDRESSED. REVISE AS
 REQUIRED.
  
 D) COORDINATE TYPE OF ROOFING SYSTEM TO BE INSTALLED
 WITH PRODUCT APPROVAL SUBMITTED. SEE APPROVED FLAT ROOF
 SYSTEM SELECTED ON NOA SUBMITTED AND REVISE AS
 REQUIRED.
  
  
 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) FLAT ROOF ASSEMBLY. NOA 08-0226.06 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA.
  
 ***NOTE: PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 AS REQUIRED BY GENERAL LIMITATION # 7 ON LAST PAGE OF
 NOA SUBMITTED. ENGINEER TO COORDINATE RAS 117
 CALCULATIONS WITH REVISED NOA.
  
 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) NEW PRODUCT APPROVAL AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 4- NEED SEPARATE PERMITS FOR ELECTRICAL, MECHANICAL,
 PLUMBING, ROOFING. OWNER BUILDER CAN SIGN ON THE PERMIT
 APPLICATION FOR THESE SUBPERMITS OR CONTRACTORS MAY
 APPLY FOR THEIR OWN SUBPERMITS. INDICATE WHICH OPTION
 IS GOING TO BE.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712