| 2012-05-11 13:17:36 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS. |
| | 2010 FLORIDA RESIDENTIAL CODE. 2010 FBC |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 405.4.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | 2- ONCE PLANS ARE REVISED, PLEASE BRING THEM TO PALM |
| | BEACH COUNTY (2300 N. JOG RD) TO VERIFY IF IMPACT FEES |
| | ARE DUE. BRING BACK STAMPED PLANS AND COPY OF PAID |
| | RECEIPT IF FEES ARE DUE. |
| | |
| | 3- REVISE BUILDING CODE AND WIND LOAD DESIGN |
| | CERTIFICATION ON SHEET 1: |
| | A) CURRENT CODE EDITION IS 2010 FLORIDA RESIDENTIAL |
| | CODE. THERE IS NOT 2009 FBC. |
| | |
| | B) REVISE BASIC WIND SPEED. 2010 FLORIDA RESIDENTIAL |
| | CODE IS BASED ON THE ULTIMATE DESIGN WIND SPEED VULT |
| | AND THE NOMINAL DESIGN WIND SPEED VASD. SEE SEC. |
| | R301.2..1.3. NOTE: CITY OF WEST PALM BEACH ULTIMATE |
| | DESIGN WIND SPEED IS 170MPH. |
| | |
| | 4- PROVIDE LICENSE NUMBER FOR CARLOS M. GONZALEZ AS |
| | REQUIRED BY CHAPTER 481 FLORIDA STATUTE. TITLE BLOCK |
| | SHOWS CARLOS GONZALEZ OFFERING THE PROFESSIONAL |
| | SERVICES OF ARCHITECTURE, PLANNING AND INTERIOR DESIGN. |
| | LICENSE IS REQUIRED BY CHAPTER 481 FLORIDA STATUTE OR |
| | REMOVE FROM TITLE BLOCK. |
| | |
| | 5- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) EXTERIOR DOOR AS SHOWN ON PLANS. |
| | |
| | B) FLAT ROOF ASSEMBLY. CLEARLY SPECIFY APPROVED |
| | ASSEMBLY AND PROVIDE THE RAS 117 CALCULATIONS AS |
| | REQUIRED BY GENERAL LIMITATION #7. |
| | ***NOTE: IF PRODUCT APPROVAL SUBMITTED REQUIRES SIGNED |
| | AND SEALED RAS 117 CALCULATIONS, THEN THOSE |
| | CALCULATIONS ARE REQUIRED TO BE SIGNED AND SEALED. |
| | |
| | C) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND |
| | PAGE SHOWING THE SPECIFIED CONNECTOR. THIS APPLIES FOR |
| | STRUCTURAL CONNECTORS ONLY. |
| | |
| | 6- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC. |
| | |
| | 7- REVISE WALL SECTION ON SHEET 1: |
| | A) SPECIFY THICKNESS OF ROOF SHEATHING. |
| | B) SPECIFY ROOF SHEATHING FASTENING. SEC. R803.2.3.1. |
| | NEED MIN. 8D RING SHANK NAILS AND ZONE 3 REQUIRES |
| | FASTENING @ 4"O.C. |
| | C) SPECIFY ROOF INSULATION. COORDINATE WITH THE ENERGY |
| | CALCULATIONS. |
| | D) SPECIFY INSIDE CEILING HEIGHT. SEC. R305. |
| | E) MINIMUM DEPTH OF CONCRETE FOOTING BELOW GRADE IS |
| | 12". CLEARLY INDICATE THE FINISH GRADE LINE AND REVISE |
| | AS REQUIRED. SEC. R403.1.4. |
| | |
| | 8- FOUNDATION PLAN: PLEASE PROVIDE COMPLETE |
| | SPECIFICATIONS FOR 8"X8" COLUMNS WITH 3000PSI CONCRETE. |
| | CLARIFY WHY THERE ARE IS NOT STEEL BAR SPECIFIED. |
| | PROVIDE ENGINEERING ANALYSIS SHOWING WHY REINFORCEMENT |
| | IS NOT REQUIRED. SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. |
| | |
| | 9- NEED SEPARATE PERMITS FOR ELECTRICAL, MECHANICAL, |
| | PLUMBING, ROOFING. OWNER BUILDER CAN SIGN ON THE PERMIT |
| | APPLICATION FOR THESE SUBPERMITS OR CONTRACTORS MAY |
| | APPLY FOR THEIR OWN SUBPERMITS. |
| | |
| | 10- ROOF FRAMING PLAN: |
| | A) PLEASE SPECIFY FROM WHICH CATALOG IS THE LUP28 JOIST |
| | HANGER TAKEN FROM?. UNABLE TO FIND IT IN THE SIMPSON |
| | CATALOG. PROVIDE PRODUCT APRPOVAL FOR THIS PRODUCT. |
| | SEC. 107.2.1.3 CITY AMENDMENTS TO FBC. |
| | |
| | 11- FLOOR TO FLOOR CONNECTION DETAIL SHOWS NEW CONCRETE |
| | SLAB AT THE SAME LEVEL AS THE EXISTING SLAB, WHILE |
| | FOUNDATION PLANS SHOWS A 6" DROP. CLARIFY AND REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |