| Plan Review Notes For Permit 12040143 |
| Permit Number |
12040143 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-06-11 11:54:21 | PROVISO | | | | | | ISSUED AT CONTRACTOR'S RISK | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | COMMENT FROM FIRST REVIEW: | | | | | | PLEASE INCLUDE WIND DESIGN CRITERIA TO SHOW COMPLIANCE | | | WITH FBC1609, WIND LOADS. CRITERIA SHOULD INCLUDE: | | | | | | V(ULT) WIND SPEED | | | EXPOSURE CLASSIFICATION | | | RISK CATEGORY | | | | | | RISK CATEGORY II, WIND SPEED 160MPH DOES NOT COMPLY | | | WITH THE MINIMUM DESIGN CRITERIA FOR THIS LOCATION: | | | | | | BASED ON LOCATION INFORMATION, THE FOLLOWING IS THE | | | MINIMUM CRITERIA REQUIRED: | | | | | | RISK CATEGORY 1 -154MPH | | | RISK CATEGORY II - 168 REQUIRED. | | | | | | REVISE PLAN PRIOR TO FIRST INSPECTION TO INCLUDE CODE | | | COMPLIANT WIND DESIGN CRITERIA. | | | | | | |
|