| Plan Review Notes For Permit 12040143 |
| Permit Number |
12040143 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-03 16:33:09 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. PROVIDE A VERIFIABLE CONTRACT SIGNED BY OWNER. | | | PERMIT VALUE IS TO INCLUDE ALL LABOR, MATERIALS, AND | | | ENGINEERING, FBC 108.3. | | | | | | 2. CODE HAS CHANGED TO FBC2010 EFFECTIVE MARCH 15. | | | PLEASE REVISE AND ELIMINATE REFERENCES TO FBC 2007. | | | | | | 3. WIND DESIGN CRITERIA STATES: "IN COMPLIANCE W/FBC | | | 2010 HIGH VELOCITY . . . DESIGNED IN ACCORDANCE WITH | | | THE FBC 2007 160MPH WIND LOAD REQ;UIREMENTS . . . WIND | | | IMPORTANCE FACTOR 1.0 . . . MEETS WIND LOAD | | | REQUIREMENTS ASCE7-10 160MPH EXPOSURE C . . . " | | | | | | THIS STATEMENT IS CONFLICTING. PALM BEACH COUNTY IS NOT | | | LOCATED IN THE HVHZ. FBC2007 160 IMPORTANCE FACTOR 1 IS | | | NOT THE SAME AS ASCE7-10 160MPH EXPOSURE C. ASCE7-10 | | | 160MPH DOES NOT HAVE AN IMPORTANCE FACTOR OF 1 (NOW | | | CALLED RISK CATEGORY). | | | | | | PLEASE INCLUDE WIND DESIGN CRITERIA TO SHOW COMPLIANCE | | | WITH FBC1609, WIND LOADS. CRITERIA SHOULD INCLUDE: | | | | | | V(ULT) WIND SPEED | | | EXPOSURE CLASSIFICATION | | | RISK CATEGORY | | | | | | ANY OTHER UNNECESSARY INFORMATION SHOULD BE REMOVED AS | | | IT IS CONFUSING. IF ENGINEER ELECTS TO KEEP IT ON THE | | | PLAN, PLEASE CONFIRM THAT IT IS CONSISTENT WITH OTHER | | | INFORMATION AND COMPLIES WITH THE MINIMUM CODE | | | REQUIREMENTS. |
|