Plan Review Notes
Plan Review Notes For Permit 12040141
Permit Number 12040141
Review Stop B
Sequence Number 1
Notes
Date Text
2012-05-03 16:19:49****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. PROVIDE A VERIFIABLE CONTRACT SIGNED BY OWNER.
 PERMIT VALUE IS TO INCLUDE ALL LABOR, MATERIALS, AND
 ENGINEERING, FBC 108.3.
  
 2. CODE HAS CHANGED TO FBC2010 EFFECTIVE MARCH 15.
 PLEASE REVISE AND ELIMINATE REFERENCES TO FBC 2007.
  
 3. WIND DESIGN CRITERIA STATES: "IN COMPLIANCE W/FBC
 2010 HIGH VELOCITY . . . DESIGNED IN ACCORDANCE WITH
 THE FBC 2007 160MPH WIND LOAD REQ;UIREMENTS . . . WIND
 IMPORTANCE FACTOR 1.0 . . . MEETS WIND LOAD
 REQUIREMENTS ASCE7-10 160MPH EXPOSURE C . . . "
  
 THIS STATEMENT IS CONFLICTING. PALM BEACH COUNTY IS NOT
 LOCATED IN THE HVHZ. FBC2007 160 IMPORTANCE FACTOR 1 IS
 NOT THE SAME AS ASCE7-10 160MPH EXPOSURE C. ASCE7-10
 160MPH DOES NOT HAVE AN IMPORTANCE FACTOR OF 1 (NOW
 CALLED RISK CATEGORY).
  
 PLEASE INCLUDE WIND DESIGN CRITERIA TO SHOW COMPLIANCE
 WITH FBC1609, WIND LOADS. CRITERIA SHOULD INCLUDE:
  
 V(ULT) WIND SPEED
 EXPOSURE CLASSIFICATION
 RISK CATEGORY
  
 ANY OTHER UNNECESSARY INFORMATION SHOULD BE REMOVED AS
 IT IS CONFUSING. IF ENGINEER ELECTS TO KEEP IT ON THE
 PLAN, PLEASE CONFIRM THAT IT IS CONSISTENT WITH OTHER
 INFORMATION AND COMPLIES WITH THE MINIMUM CODE
 REQUIREMENTS.