2012-04-06 12:59:1204/06/2012
 PERMIT #12040126
 601 CLEARWATER PARK ROAD
  
 PLANS REVIEWED BY FIRE (PASSED)
  
 * LOSS OF POWER TO THE PART OF THE ACCES CONTROL SYSTEM
 THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK THE
 DOORS IN THE DIRECTION OF EGRESS.
  
 * THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
  
 * ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY REST.
  
  
 RONALD E. FERGUSON ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW