| Date |
Text |
| 2012-04-12 14:32:47 | 501 FERN STREET |
| | PERMIT #12040122 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | CONSTRUCTION AND DEMOLITION ACTIVITIES SHALL COMPLY |
| | WITH THE 2010 EDITION OF THE FLORIDA FIRE PREVENTION |
| | CODE WHICH CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND |
| | NFPA 101 WITH FLORIDA AMENDMENTS. |
| | |
| | ALL DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. |
| | |
| | PLANS REFERENCE TWO SHEETS THAT WERE NOT PROVIDED |
| | (SHEET 1A-1 AND SHEET 1A-2). |
| | |
| | PROVIDE A LIFE SAFETY PLAN INDICATING EXIT DOORS, FIRE |
| | RATED DOORS AND WALLS, PORTABLE FIRE EXTINGUISHERS, |
| | EXIT SIGNS, EMERGENCY LIGHTING, TRAVEL DISTANCES, |
| | COMMON PATH OF TRAVEL ETC. |
| | |
| | PLAN NOTE 71 INDICATES FIRE SPRINKLERS AND EQUIPMENT TO |
| | BE RELOCATED. NO ENGINEERING DRAWINGS WERE PROVIDED |
| | SHOWING THIS SCOPE OF WORK. |
| | |
| | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING |
| | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A |
| | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN |
| | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE |
| | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST |
| | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF |
| | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. |
| | |
| | SHEET E-1: BUILDINGS LABELS "A" AND "B" ARE SWITCHED |
| | WHEN COMPARED TO OTHER SHEETS. THIS SHEET SHOWS ONLY |
| | ONE EXIT FOR EACH BUILDING. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |