| 2012-04-12 07:42:08 | BUILDING PLAN REVIEW |
| | PERMIT: 12040122 |
| | ADD: 501 FERN ST SUITE B |
| | CONT: AUTOBUILDERS |
| | TEL: (561)722-3956 |
| | |
| | 2010FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH AMENDMENTS |
| | S-2 OCCUPANCY |
| | BUILDING TYPE: IIIB |
| | SPRINKLERED |
| | |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS 1A-3 DO NOT INDICATE TO WHAT EDITION OF CODE |
| | THE PLANS WERE DESIGNED TOO? ADMINISTRATIVE CODE |
| | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR PLAN REVIEW. |
| | |
| | 2) PLANS S-2 DO NOT INDICATE THE WIND DESIGN CRITERIA |
| | NOR THE WIND SPEED THIS BUILDING WAS DESIGNED TOO? 2010 |
| | FBC-B 1609.1.1. |
| | 1609.6.2 WIND DESIGN PROCEDURES |
| | 2.1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| | ASSUMED TO COME FROM ANY HORIZONTAL DIRECTION. |
| | 2.2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | 2.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. |
| | 2.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| | 2.5) WALL PRESSURES POSITIVE & NEGATIVE |
| | |
| | 3) SHEET 1A-3 BUILDING DATA INDICATES THIS IS A TYPE |
| | III-B FULLY SPRINKLERED BUILDING, BUT NOTE # 16 |
| | INDICATES FIRE SPRINKLER WORK TO BE COMPLETED BY THE |
| | FUTURE TENANT. WHAT IS THE TOTAL SQ FT OF THE BUILDING? |
| | ARE AREA INCREASES FOR SPRINKLERS BEING TAKEN? IS THIS |
| | SYSTEM A FULLY FUNCTIONAL SYSTEM? |
| | |
| | 4) SHEET R-1, IS THE TOTAL SQ FT OF THE BUILDING TO BE |
| | CONSIDERED A S-2 OCCUPANCY OR ISTHIS A MIXED USE |
| | OCCUPANCY? PLANS DO NOT INDICATE IF THE WALL BETWEEN |
| | WAREHOUSE A & B SHALL BE A TENANT SEPERATION WALL OR IF |
| | IT MAY REQUIRED TO BE A OCCUPANCY SEPERATION WALL? 2010 |
| | FBC-B ADMINISTRTIVE CODE 106.3.5 MINIMUM PLAN REVIEW |
| | CRITERIA. |
| | |
| | 5) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 6) MISSING PRODUCT APPROVALS |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(A) EXTERIOR DOORS. |
| | (B) WINDOWS |
| | (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL |
| | LOUVERS, EFIS SYSTEMS, |
| | (D) ROOFING PRODUCTS AND ASSEMBLIES |
| | (E) SHUTTERS |
| | (F) SKYLIGHTS |
| | (G) PRE-ENGINEERED A/C STANDS |
| | |
| | 7) PLEASE BE AWARE OF MIAMI-DADE NOA DECK LIMITATIONS |
| | FOR SPANS BETWEEN BAR JOIST SEE DECK LIMITATION # 2 |
| | DECK SPANS EVERY 5 FT. THE CURRENT SHEET S-2 BAR JOIST |
| | SPACING DOES EXCEED 5'-0" ON CENTER, THIS MAY DEPEND ON |
| | THE GUAGE OF SHEET METAL DECKING TO BE INSTALLED! |
| | BEWARE.106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 8) S-2 INDICATES WHAT APPEARS TO BE ROOF FRAMING FOR |
| | ROOF TOP PACKAGE UNITS PLEASE PROVIDE CURB INFORMATION |
| | AND ANCHORAGE FOR THE CURBS. IF PACKAGE UNITS ARE TO BE |
| | INCORPORATED INTO THIS PERMIT PLEASE PROVIDE ANCHORAGE |
| | TO CURB. FBC-B 1609. COMPONENTS & CLADDING. |
| | |
| | 9) SHEET S-3 INDICATES ROOF TOP ELEVATIONS ABOVE 16 |
| | FEET BE AWARE OF 2010 FBC-M 306.5 WHERE EQUIPMENT AND |
| | APPLIANCES REQUIRING ACCESS ARE INSTALLED ON ROOFS OR |
| | ELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET (4877 |
| | MM), SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT |
| | APPROVED MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE |
| | FROM GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND |
| | APPLIANCES' LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT |
| | REQUIRE CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 |
| | INCHES (762 MM) HIGH. |
| | |
| | 10) 1013.5 MECHANICAL EQUIPMENT. GUARDS SHALL BE |
| | PROVIDED WHERE APPLIANCES, EQUIPMENT, FANS, ROOF HATCH |
| | OPENINGS OR OTHER COMPONENTS THAT REQUIRE SERVICE ARE |
| | LOCATED WITHIN 10 FEET (3048 MM) OF A ROOF EDGE OR OPEN |
| | SIDE OF A WALKING SURFACE AND SUCH EDGE OR OPEN SIDE IS |
| | LOCATED MORE THAN 30 INCHES (762 MM) ABOVE THE FLOOR, |
| | ROOF OR GRADE BELOW. THE GUARD SHALL BE CONSTRUCTED SO |
| | AS TO PREVENT THE PASSAGE OF A 21-INCH-DIAMETER (533 |
| | MM) SPHERE. THE GUARD SHALL EXTEND NOT LESS THAN 30 |
| | INCHES (762 MM) BEYOND EACH END OF SUCH APPLIANCE, |
| | EQUIPMENT, FAN OR COMPONENT. |
| | |
| | 11) 1013.6 ROOF ACCESS. GUARDS SHALL BE PROVIDED WHERE |
| | THE ROOF HATCH OPENING IS LOCATED WITHIN 10 FEET (3048 |
| | MM) OF A ROOF EDGE OR OPEN SIDE OF A WALKING SURFACE |
| | AND SUCH EDGE OR OPEN SIDE IS LOCATED MORE THAN 30 |
| | INCHES (762 MM) ABOVE THE FLOOR, ROOF OR GRADE BELOW. |
| | THE GUARD SHALL BE CONSTRUCTED SO AS TO PREVENT THE |
| | PASSAGE OF A 21-INCH-DIAMETER (533 MM) SPHERE. |
| | |
| | 12) CONTRACTOR TO COME IN BEFORE ISSUANCE OF PERMT TO |
| | INDICATE UNDER SCOPE OF WORK ON THE PERMIT APPLICATION |
| | "SHELL ONLY". |
| | |