| 2012-04-10 16:06:35 | COMMENTS FOR MASTER PACKAGE. | | | RESIDENTIAL (R2) RE-ROOF BUILDING REVIEW. | | | 2010 FBC. | | | | | | ***NOTE: USING THIS PERMIT APPLICATION AS MASTER FOR | | | ALL RE-ROOF PERMITS WITH IDENTICAL DESCRIPTION. PLEASE | | | PROVIDE THREE COMPLETE PACKAGES. ONE APPROVED PACKAGE | | | WILL STAY IN OUR FILE AND THE OTHER TWO WILL BE GIVEN | | | TO THE CONTRACTOR TO BE USED IN THE FIELD. | | | | | | 1- THE FBC 2010 WENT INTO EFFECT ON MARCH 15, 2012. | | | ENGINEER NEEDS TO UPDATE/REVISE THE RAS 117 | | | CALCULATIONS USING THE 2010 FBC. | | | | | | 2- FOR YOUR INFORMATION FLAT ROOF NOA 07-1018.10 | | | SUBMITTED EXPIRES THIS YEAR ON AUGUST 22, 2012. THAT | | | MEANS THAT THIS MASTER WILL BE VOID AFTER THAT DATE AND | | | A NEW MASTER WILL BE REQUIRED. | | | | | | 3- PLEASE PROVIDE A FIELD WITHDRAWAL RESISTANCE TEST | | | (TAS 105) AS REQUIRED BY GENERAL LIMITATION #5 ON LAST | | | PAGE OF NOA SUBMITTED. | | | | | | ***NOTE: IF THE FIELD TESTED VALUE OF THE FASTENER IS | | | LESS THAN 275 LBF, THEN INSULATION ATTACHMENT SHALL NOT | | | BE ACCEPTABLE. SEE GENERAL LIMITATION #5. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|