Plan Review Notes
Plan Review Notes For Permit 12040097
Permit Number 12040097
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-06-05 10:51:362481 OKEECHOBEE BOULEVARD
 PERMIT #12040097
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO
 THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION
 DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. SMOKING
 SHALL BE PROHIBITED EXCEPT IN DESIGNATED EXTERIOR
 AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 WHERE SMOKING IS PERMITTED, SAFE RECEPTACLES FOR
 SMOKING MATERIALS SHALL BE PROVIDED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 A KNOX-BOX KEY SAFE CAN BE ORDERED FROM
 WWW.KNOXBOX.COM.
  
 PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH
 EXIT SIGNS.
  
 EXIT DOORS EQUIPPED WITH DELAYED EGRESS LOCKING SYSTEMS
 SHALL COMPLY WITH THE FOLLOWING:
 1) UNLOCK UPON ACTUATION OF THE FIRE SPRINKLER OR FIRE
 ALARM SYSTEM
 2) UNLOCK UPON LOSS OF POWER CONTROLLING THE LOCKING
 MECHANISM
 3) AN IRREVERSIBLE PROCESS SHALL RELEASE THE LOCK
 WITHIN 15 SECONDS, UPON APPLICATION OF A FORCE TO THE
 RELEASE DEVICE REQUIRED IN 7.2.1.5.9 UNDER THE
 FOLLOWING CONDITIONS:
 (A) THE FORCE SHALL NOT BE REQUIRED TO EXCEED 15 LBF
 (67 N).
 (B) THE FORCE SHALL NOT BE REQUIRED TO BE CONTINUOUSLY
 APPLIED FOR MORE THAN 3 SECONDS.
 (C) THE INITIATION OF THE RELEASE PROCESS SHALL
 ACTIVATE AN AUDIBLE SIGNAL IN THE VICINITY OF THE DOOR
 OPENING.
 (D) ONCE THE LOCK HAS BEEN RELEASED BY THE APPLICATION
 OF FORCE TO THE RELEASING DEVICE, RELOCKING SHALL BE BY
 MANUAL MEANS ONLY.
 (4)A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. HIGH AND NOT LESS THAN 1/8 IN. IN STROKE
 WIDTH ON A CONTRASTING BACKGROUND THAT READS AS FOLLOWS
 SHALL BE LOCATED ON THE DOOR LEAF ADJACENT TO THE
 RELEASE DEVICE: "PUSH UNTILALARM SOUNDS DOOR CAN BE
 OPENED IN 15 SECONDS"
  
 EXIT DOORS EQUIPPED WITH POWERED DOOR LEAF OPERATION
 SHALL COMPLY WITH THE FOLLOWING:
 1) IN THE EVENT OF POWER FAILURE, THE LEAVES OPEN
 MANUALLY TO ALLOW EGRESS TRAVEL OR CLOSE WHEN NECESSARY
 TO SAFEGUARD THE MEANS OF EGRESS.
 2) THE FORCE REQUIRED TO SET THE LEAF IN MOTION SHALL
 NOT EXCEED 50 LBF (222 N).
 3) THE DOOR ASSEMBLY SHALL BE DESIGNED AND INSTALLED SO
 THAT, WHEN A FORCE IS APPLIED TO THE DOOR LEAF ON THE
 SIDE FROM WHICH EGRESS IS MADE, IT SHALL BE CAPABLE OF
 SWINGING FROM ANY POSITION TO PROVIDE FULL USE OF THE
 REQUIRED WIDTH OF THE OPENING IN WHICH IT IS INSTALLED.
 4) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS
 THAN 1 IN. HIGH ON A CONTRASTING BACKGROUND THAT READS
 AS FOLLOWS SHALL BE LOCATED ON THE EGRESS SIDE OF EACH
 DOOR OPENING: "IN EMERGENCY - PUSH TO OPEN"
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE