| | 1. VERIFY THE ELECTRICAL SERVICE MAINS FOR THIS |
| | BUILDING ARE SIX OR LESS AND GROUPED IN ONE LOCATION. |
| | THE SITE PLANS SUGGEST THIS BUILDING MAY ALREADY BE |
| | SERVED FROM ANOTHER LOCATION. NEC 230.2, 230.71, 230.72 |
| | 2. PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 |
| | 3. PROVIDE A LIGHTING DENSITY CALCULATION VERIFYING |
| | COMPLIANCE WITH THE 2010 FLORIDA BUILDING ENERGY CODE |
| | REQUIREMENTS. FBC EC 505.5.3 |
| | 4. PROVIDE A DETAIL WHICH PROVIDES A DEDICATED WORKING |
| | SPACE FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS. |
| | NEC 110.26, 240.24, 408.17 |
| | 5. A GFCI GENERAL PURPOSE RECEPTACLE IS REQUIRED AT AN |
| | ACCESSIBLE LOCATION FOR THE SERVICE OF HEATING, AIR |
| | CONDITIONING, AND REFRIGERATION EQUIPMENT LOCATED ON |
| | THE ROOF. NEC 210.63 |
| | 6. PROVIDE THE SPECIFICATIONS AND LISTINGS FOR THE |
| | GENERATOR QUICK CONNECT. NEC 90.7 |
| | 7. VERIFY LISTING BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY (NRTL) FOR THE FACTORY WIRED ?POWER WALL? |
| | ASSEMBLIES NOTED ON THE PLANS AS PANEL BOARD L1AND L2. |
| | NEC 90.7, 215.5 |
| | 8. VERIFY LISTING BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY OF THE FACTORY WIRED ?PROTOCOL RACK? |
| | ASSEMBLY NOTED ON THE PLANS FOR REFRIGERATION. NEC 90.7 |
| | 9. VERIFY LISTING BY A NATIONALLY RECOGNIZED TESTING |
| | LABORATORY OF THE OWNER SUPPLIED UPS. NEC 90.7 |
| | 10. PROVIDE A SAFETY LABELING SCHEDULE FOR THE |
| | ELECTRICAL EQUIPMENT WHICH INCLUDES SPECIFIC WORDING |
| | REGARDING THE SIZE AND TYPE OF HAZARDS. NEC 110.22, |
| | 110.16 |
| | |
| | NOTE: |
| | SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE |
| | ALARM SYSTEM, SECURITY, VOICE AND DATA. |
| | |