 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE THE ADDRESS OF THE PROJECT AND THE DESIGNER OF
 RECORD INFORMATION ON THE PLANS.
  
 IT IS NOT CLEAR FROM THE PLAN WHERE THE NEW STORAGE
 ROOM IS TO BE BUILT. IS THE "REPAIR AREA" INTENDED TO
 BE THE LOCATION OF THE STORAGE ROOM?
  
 THE PLAN INDICATES A HOPPER AND DUST COLLECTION SYSTEM.
 PROVIDE ADDITIONAL INFORMATION ON THE EQUIPMENT AND
 FUNCTION OF THIS ROOM.
  
 INDICATE IF ANY FIRE SPRINKLERS ARE EXISTING AND NEED
 TO BE ADDED OR RELOCATED.
  
 THE LOCK/LATCH RELEASING MECHANISM ON ALL DOORS SHALL
 OPEN THE DOOR WITH NOT MORE THAN ONE RELEASING
 OPERATION. THE RELEASING MECHANISM SHALL HAVE AN
 OBVIOUS METHOD OF OPERATION THAT IS READILY OPERATED
 UNDER ALL LIGHTING CONDITIONS. THE RELEASING DEVICE
 SHOULD BE CAPABLE OF BEING OPERATED WITH ONE HAND AND
 SHOULD NOT REQUIRE TIGHT GRASPING, TIGHT PINCHING OR
 TWISTING OF THE WRIST TO OPERATE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  