Plan Review Notes
Plan Review Notes For Permit 12040087
Permit Number 12040087
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-16 12:07:30BUILDING PLAN REVIEW
 PERMIT:
 ADD:
 CONT:
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) THE CONTRACTOR OF RECORD THAT IS RESPONSIBLE FOR
 THEIR PLAN FOR WHICH DISCIPLINE THEY ARE LICENSED SHALL
 PRINT THIER NAME, SIGN THEIR NAME & LICESE NUMBER TO
 THE PLANS.
 106.1.1.
  
 2) PLEASE PROVIDE A FLOOR PLAN OF THE COMPLETE TENANT
 SPACE AND THE LOCATION OF THE NEW STORAGE ROOM WITHIN
 THE WAREHOUSE. FLOOR PLAN. 106.3.5.1.1 MINIMUM CRITERIA
 FOR COMMERCIAL PLAN REVIEW.
  
 3) THE SECOND SHEET OF THE PLANS INDICATES THE USE OF A
 HOPPER AND DUST COLLECTION SYSTEM,IS THIS PART OF THE
 NEW STORAGE ROOM? OR THIS ANOTHER AREA OF WORK TO BE
 COMPLETED UNDER THIS PERMIT? PLEASE PROVIDE ADDITIONAL
 INFOR MATION ON THE HOPPER AND DUST COLLECTION SYSTEM,
 WHAT TYPES OF DUST ARE TO BE REMOVED?
  
 2010 FBC-B COMBUSTIBLE DUST TABLE 414.5 SEE FOOTNOTE"C"
  
  
 [F] 415.8.2.1 HAZARDOUS MATERIALS IN FABRICATION AREAS.
  
 [F] 415.8.2.1.1 AGGREGATE QUANTITIES. THE AGGREGATE
 QUANTITIES OF HAZARDOUS MATERIALS STORED AND USED IN A
 SINGLE FABRICATION AREA SHALL NOT EXCEED THE QUANTITIES
 SET FORTH IN TABLE 415.8.2.1.1.
  
 EXCEPTION: THE QUANTITY LIMITATIONS FOR ANY HAZARD
 CATEGORY IN TABLE 415.8.2.1.1 SHALL NOT APPLY WHERE THE
 FABRICATION AREA CONTAINS QUANTITIES OF HAZARDOUS
 MATERIALS NOT EXCEEDING THE MAXIMUM ALLOWABLE
 QUANTITIES PER CONTROL AREA ESTABLISHED BY TABLES
 307.1(1) AND 307.1(2).
  
 [F] 415.8.2.1.2 HAZARDOUS PRODUCTION MATERIALS. THE
 MAXIMUM QUANTITIES OF HAZARDOUS PRODUCTION MATERIALS
 (HPM) STORED IN A SINGLE FABRICATION AREA SHALL NOT
 EXCEED THE MAXIMUM ALLOWABLE QUANTITIES PER CONTROL
 AREA ESTABLISHED BY TABLES 307.1(1) AND 307.1(2).
  
 [F] 415.8.2.2 SEPARATION. FABRICATION AREAS, WHOSE
 SIZES ARE LIMITED BY THE QUANTITY OF HAZARDOUS
 MATERIALS ALLOWED BY TABLE 415.8.2.1.1, SHALL BE
 SEPARATED FROM EACH OTHER, FROM CORRIDORS AND FROM
 OTHER PARTS OF THE BUILDING BY NOT LESS THAN 1-HOUR
 FIRE BARRIERS.
  
 2010 FBC-B TABLE 415.8.2.1.1 COMBUSTIBLE DUST NOTE B
 B. QUANTITY OF HAZARDOUS MATERIALS IN A SINGLE
 FABRICATION SHALL NOT EXCEED THE MAXIMUM ALLOWABLE
 QUANTITIES PER CONTROL AREA IN TABLES 307.1(1) AND
 307.1(2).
  
 2010 FBC-M 510 WOODWORKING FACILITIES.
 EQUIPMENT OR MACHINERY LOCATED INSIDE BUILDINGS AT
 LUMBER YARDS AND WOODWORKING FACILITIES WHICH GENERATES
 OR EMITS COMBUSTIBLE DUST SHALL BE PROVIDED WITH AN
 APPROVED DUST-COLLECTION AND EXHAUST SYSTEM INSTALLED
 IN CONFORMANCE WITH THIS SECTION AND THE FLORIDA FIRE
 PREVENTION CODE . EQUIPMENT AND SYSTEMS THAT ARE USED
 TO COLLECT, PROCESS OR CONVEY COMBUSTIBLE DUSTS SHALL
 BE PROVIDED WITH AN APPROVED EXPLOSION-CONTROL SYSTEM.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  