| Plan Review Notes For Permit 12040085 |
| Permit Number |
12040085 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-07-09 12:14:54 | BUILDING PLAN REVIEW | | | PERMIT:12040085 | | | ADD: 4312 PINEWOOD | | | CONT: ANCHOR GENERAL CONTRACTING | | | TEL: (561)386-1266 | | | | | | 2010 FLORIDA BUILDING CODE- RESIDENTIAL W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | RESIDENTIAL PLUMBING | | | | | | 1) THE PLUMBING ISOMETRIC FOR WASTE IS DRAWN | | | INCORRECTLY: | | | 1A) HAND DRAWN IS INDICATED A SECOND SINK, THERE IS | | | ONLY ONE SINK SHOWN ON THE FLOOR PLAN, WHAT IS | | | MISLABLED IS THE HAND DRAWN SINK, IT IS PROBABLY THE | | | MISSING LAVATORY. | | | 2010 FBC-R 3108.1. | | | 1B) THE PLUMBING RISER HAS THE KITCHEN SINK TYING IN | | | BEFORE THE WET VENT IT SHOULD TIE INTO THE MAIN | | | BUILDING DRAIN AFTER THE WET VENT. | | | 2010 FBC-R 3108.1. | | | 1C) THE STACK AS DRAWN IS DIRECTLY BEHIND THE SINK | | | WHICH WOULD PLACE IT DIRECTLY IN THE MIDDLE OF THE | | | WINDOW, IT SHOULD BE ON ONE SIDE OF THE WINDOW. | | | 107.3.5 MINIMUM CRITERIA PLAN REVIEW. | | | 2) NO INFORMATION WAS PROVIDED ON THE PLUMBING AND | | | SAFETY DEVICES FOR THE WATER HEATER. | | | 2010 FBC-R 2805.1 PAN REQUIRED/ P2803.1 & 2803.6.1 | | | REQUIREMENTS FOR DISCHARGE PIPE. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | |
|