| Notes |
| Date |
Text |
| 2012-04-23 14:57:03 | 12040085 | | | 4312 PINEWOOD AVE. | | | INTERIOR RENOVATION | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | FOR THE NEW WALL SPACES ADD RECEPTACLES SO THAT NO WALL | | | SPACE IS MORE THAN 6 FEET FROM A RECEPTACLE AND ALL | | | WALL SPACES MORE THAN 2 FEET IN WIDTH HAVE A RECEPTACLE | | | I.E. NEW CLOSET WALL. NEC 210.52 | | | ALL NEW GENERAL PURPOSE OUTLETS INCLUDING THOSE IN THE | | | BEDROOMS AND SMOKE ALARMS MUST BE AFCI PROTECTED. NEC | | | 210.12 | | | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.11 | | | RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG | | | THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | | RECEPTACLE OUTLET. NEC 210.52 | | | THE NEW LIVING AREA REQUIRES A SWITCHED RECEPTACLE OR | | | LIGHT AND A SWITCHED LIGHT AT OUTSIDE ENTRANCES. A GFCI | | | PROTECTED RECEPTACLE IS REQUIRED OUTSIDE FRONT AND | | | BACK. NEC 210.70 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|