| Plan Review Notes For Permit 12040077 |
| Permit Number |
12040077 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-03 16:22:20 | RESIDENTIAL (R3) RE-ROOF REVISION BUILDING REVIEW | | | COMMENTS | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- FLAT ROOF NOA NOA 07-1219.09 SUBMITTED: | | | A) SPECIFY WHICH APPROVED ASSEMBLY IS GOING TO BE | | | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN | | | PRESSURES OF SEC. R301.2.1.4.3. | | | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS AS | | | REQUIRED BY GENERAL LIMITATION #7. | | | | | | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS | | | PERMIT IS UNDER FBC 2007 AND THAT THIS BUILDING IS | | | LOCATED ON EXPOSURE "C". | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|