| 2012-04-24 14:45:27 | FBC 2010 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. BUILDING 100 DOES NOT INCLUDE THE REQUIRED DRINKING |
| | FOUNTIAN. PLUMBING 403.1 MINIMUM PLUMBING FIXTURES. PER |
| | ACCESSIBILITY CODE 2010 - 211.2 MINIMUM NUMBER. NO |
| | FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| | ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| | 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| | 602.7. |
| | EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| | WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| | FOUNTAINS. |
| | |
| | 2. THE LAVS IN ROOMS 107 & 108 APPEAR TO BE IN THE 5' |
| | CLEAR SPACE FOR THE WATER CLOSET. THE TOTAL FOR THE |
| | RESTROOM WOULD BE 5' + 2'-1" = 7'-1" |
| | FBC 2010 FLORIDA ACCESSIBILITY CODE 604.3.1 SIZE. |
| | CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES |
| | (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| | WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED |
| | PERPENDICULAR FROM THE REAR WALL. 604.3.2 OVERLAP. THE |
| | REQUIRED CLEARANCE AROUND THE WATER CLOSET SHALL BE |
| | PERMITTED TO OVERLAP THE WATER CLOSET, ASSOCIATED GRAB |
| | BARS, DISPENSERS, SANITARY NAPKIN DISPOSAL UNITS, COAT |
| | HOOKS, SHELVES, ACCESSIBLE ROUTES, CLEAR FLOOR SPACE |
| | AND CLEARANCES REQUIRED AT OTHER FIXTURES, AND THE |
| | TURNING SPACE. NO OTHER FIXTURES OR OBSTRUCTIONS SHALL |
| | BE LOCATED WITHIN THE REQUIRED WATER CLOSET CLEARANCE. |
| | |
| | 3. A SANITARY RISER DIAGRAM IS REQUIRED PER FBC 106.3.3 |