| Plan Review Notes For Permit 12040043 |
| Permit Number |
12040043 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-05-02 16:57:31 | RESIDENTIAL (R3) ALTERATION PLUMBING REVIEW COMMENTS. | | | 2010 FBC- RESIDENTIAL. | | | | | | 1- PLEASE PROVIDE PLUMBING RISER DIAGRAM THAT MATCHES | | | FLOOR PLAN. SEC. 107.3.5.2(11) OF CITY AMENDMENTS TO | | | FBC. | | | | | | 2- REVISE PLUMBING RISER DIAGRAM SUBMITTED. NO MORE | | | THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE | | | UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION. | | | SEC. P3108.2.1. | | | | | | 3- PLUMBING RISER DIAGRAM MAY BE DRAWN BY THE PLUMBING | | | CONTRACTOR DOING THE JOB. PROVIDE CONTRACTOR'S NAME, | | | LICENSE NUMBER AND SIGN DRAWINGS. SEC 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | |
|