2012-05-02 16:57:31RESIDENTIAL (R3) ALTERATION PLUMBING REVIEW COMMENTS.
 2010 FBC- RESIDENTIAL.
  
 1- PLEASE PROVIDE PLUMBING RISER DIAGRAM THAT MATCHES
 FLOOR PLAN. SEC. 107.3.5.2(11) OF CITY AMENDMENTS TO
 FBC.
  
 2- REVISE PLUMBING RISER DIAGRAM SUBMITTED. NO MORE
 THAN ONE WET-VENTED FIXTURE DRAIN SHALL DISCHARGE
 UPSTREAM OF THE DRY-VENTED FIXTURE DRAIN CONNECTION.
 SEC. P3108.2.1.
  
 3- PLUMBING RISER DIAGRAM MAY BE DRAWN BY THE PLUMBING
 CONTRACTOR DOING THE JOB. PROVIDE CONTRACTOR'S NAME,
 LICENSE NUMBER AND SIGN DRAWINGS. SEC 107.2.1 CITY
 AMENDMENTS TO FBC.
  