2012-05-02 16:55:53RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS.
 2010 FBC-RESIDENTIAL.
  
 1- FLOOR PLANS SUBMITTED SHOW INTERIOR BEDROOM WITH NO
 WINDOWS. NEED TO PROVIDE EMERGENCY EGRESS TO THIS
 BEDROOM AS REQUIRED BY SEC. 601.2 OF 2010 FBC-EXISTING
 BUILDING AND SEC. R310.
  
 2- SPECIFY SAFETY GLASS ON BATHROOM WINDOW LOCATED BY
 THE TUB AREA. SEC. 601.2 OF 2010 FBC-EXISTING BUILDING
 CODE AND SEC. R308.4 OF 1020 FLORIDA RESIDENTIAL CODE.
 ***NOTE: IF EXISTING WINDOW IS IMPACT WINDOW, THEN IT
 MEETS THE SAFETY GLASS REQUIREMENTS. OTHERWISE, PRODUCT
 APPROVAL IS REQUIRED.
  
 3- ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING IS
 LOCATED ON EXPOSURE "D". DESIGN PRESSURES SHOWN ON
 SHEET #1 DON'T CORRESPOND TO EXPOSURE "D". REVISE THE
 DESIGN PRESSURES AND SPECIFY THE BUILDING EXPOSURE.
  