| 2012-05-02 16:55:53 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW COMMENTS. | | | 2010 FBC-RESIDENTIAL. | | | | | | 1- FLOOR PLANS SUBMITTED SHOW INTERIOR BEDROOM WITH NO | | | WINDOWS. NEED TO PROVIDE EMERGENCY EGRESS TO THIS | | | BEDROOM AS REQUIRED BY SEC. 601.2 OF 2010 FBC-EXISTING | | | BUILDING AND SEC. R310. | | | | | | 2- SPECIFY SAFETY GLASS ON BATHROOM WINDOW LOCATED BY | | | THE TUB AREA. SEC. 601.2 OF 2010 FBC-EXISTING BUILDING | | | CODE AND SEC. R308.4 OF 1020 FLORIDA RESIDENTIAL CODE. | | | ***NOTE: IF EXISTING WINDOW IS IMPACT WINDOW, THEN IT | | | MEETS THE SAFETY GLASS REQUIREMENTS. OTHERWISE, PRODUCT | | | APPROVAL IS REQUIRED. | | | | | | 3- ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING IS | | | LOCATED ON EXPOSURE "D". DESIGN PRESSURES SHOWN ON | | | SHEET #1 DON'T CORRESPOND TO EXPOSURE "D". REVISE THE | | | DESIGN PRESSURES AND SPECIFY THE BUILDING EXPOSURE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|