| Plan Review Notes For Permit 12040042 |
| Permit Number |
12040042 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-06-01 13:15:27 | FBC 2010 PLUMBING REVIEW #2 | | | | | | ITEM #4 HAS NOT BEEN ADDRESSED. SHEET A-0.0 LISTS | | | EDUCATION NUMBER OF OCCUPANTS AT 271 AND ADMINISTRATION | | | AT 60. WITH A TOTAL OF 331, FOUR DRINKING FOUNTAINS | | | WOULD BE REQUIRED. ALSO NOTE THAT WATER COOLERS OR | | | BOTTLED WATER DISPENSERS COULD SUBSTITUTE FOR 50% (2) | | | OF THE DRINKING FOUNTAINS. | | | | | | 4. THE TOTAL OCCUPANT LOAD FOR BUILDING APPEARS TO BE | | | OVER 300. 4 DRINKING FOUNTAINS WILL BE REQUIRED. 2 ARE | | | REQUIRED TO BE ACCESSIBLE. | | | NOTE: 410.1 APPROVAL. DRINKING FOUNTAINS...IN OTHER | | | OCCUPANCIES, WHERE DRINKING FOUNTAINS ARE REQUIRED, | | | WATER COOLERS OR BOTTLED WATER DISPENSERS SHALL BE | | | PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50 | | | PERCENT OF THE REQUIRED DRINKING FOUNTAINS. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|