| Date |
Text |
| 2012-04-09 15:08:59 | 1711 WORTHINGTON ROAD - BUILDING A & B |
| | PERMIT #12040042 & #12040044 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE SCOPE OF WORK APPEARS TO INCLUDE A CHANGE OF |
| | OCCUPANCY. SUBMIT DEMOLITION DRAWINGS. ALL DEMOLITION |
| | WORK SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. |
| | TRASH AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE |
| | SITE DAILY. POST "NO SMOKING" SIGNS THROUGHOUT |
| | BUILDING. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| | CONTRAST THE BACKGROUND. |
| | |
| | INDICATE THE OCCUPANCY TYPE AND FIRE RATED SEPARATION |
| | BETWEEN SUITE #108 AND THE AREA TO THE WEST OF THIS |
| | SUITE. EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION |
| | SHALL BE PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING READING FIRE/SMOKE BARRIER-PROTECT ALL |
| | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN |
| | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE |
| | SPACED NOT MORE THAN 15 FEET ON CENTER. |
| | |
| | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL |
| | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| | |
| | INTERIOR WALL AND CEILING FINISH MATERIALS SHALL BE |
| | EITHER CLASS A OR CLASS B PER SECTION 14.3.3.2 OF NFPA |
| | 101 (FLORIDA). |
| | |
| | CONFIRM THE LARGE MOTIVATIONAL POSTERS/SIGNS IN THE |
| | EGRESS CORRIDORS MEET THE REQUIREMENTS FOR CLASS A OR |
| | CLASS B INTERIOR WALL FINISHES. |
| | |
| | RETRACTABLE BELT BARRIER OBSTRUCTS PATH OF EGRESS TO |
| | EXIT DOORS. |
| | |
| | THE CURRENT SHELL SPACE (FUTURE CLASSROOMS #7 & #8) |
| | WILL BE TREATED AS A STORAGE ROOM UNTIL THIS SPACE IS |
| | OCCUPIED. THE STORAGE ROOM WILL NEED TO BE SEPARATED |
| | FROM THE REST OF THE BUILDING WITH A ONE-HOUR FIRE |
| | BARRIER HAVING PROTECTED OPENINGS AND PENETRATIONS. |
| | |
| | FUTURE CLASSROOM #8 SHOWS FURNITURE OBSTRUCTING THE |
| | EXTERIOR EXIT DOOR. |
| | |
| | ARTWORK AND TEACHING MATERIALS ATTACHED TO THE WALLS |
| | SHALL NOT EXCEED 20 PERCENT OF THE INDIVIDUAL WALL |
| | AREA. |
| | |
| | AN EMERGENCY PLAN TO BE DEVELOPED AND POSTED IN |
| | BUILDING PRIOR TO OCCUPANCY. |
| | |
| | EMERGENCY EGRESS DRILLS SHALL BE CONDUCTED MONTHLY. ALL |
| | DRILLS SHALL BE SOUNDED ON THE FIRE ALARM SYSTEM. |
| | |
| | FIRE PREVENTION INSPECTIONS SHALL BE CONDUCTED MONTHLY |
| | BY A TRAINED SENIOR MEMBER OF THE STAFF, AFTER WHICH A |
| | COPY OF THE LATEST INSPECTION REPORT SHALL BE POSTED IN |
| | A CONSPICUOUS PLACE IN THE DAY-CARE FACILITY. IT SHALL |
| | BE THE DUTY OF THE STAFF TO INSPECT ALL EXITS DAILY TO |
| | ENSURE THAT ALL DOORS AND EXIT PATHS ARE MAINTAINED |
| | CLEAR OF OBSTRUCTIONS. |
| | |
| | FIRE ALARM: PROVIDE NOTIFICATION APPLIANCES IN ALL |
| | PUBLIC AND COMMON USE SPACES SUCH AS READING #123, |
| | BREAK #129, ETC. |
| | |
| | FIRE ALARM: A CERTIFICATE OF COMPLETION AND A THIRD |
| | PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE |
| | SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM |
| | INSPECTION. |
| | |
| | WESLEY JOLIN |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |