| Plan Review Notes For Permit 12040042 |
| Permit Number |
12040042 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-23 17:23:37 | 12040044 & 12040042 | | | 1700 WORTHINGTON ROAD | | | BLDG. A & B | | | | | | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC 13-415 ABC.5 | | | VERIFY COMPLIANCE WITH LIGHTING AND GLARE REQUIREMENTS | | | FOR CLASS ROOMS. FBC 443.3.7 | | | PROVIDE A RISER PLAN SHOWING THE NEW AND EXISTING | | | ELECTRIC SERVICE COMPONENTS WITH MAIN DISCONNECT, | | | SERVICE GROUNDING, CONDUIT SIZE AND TYPE, CONDUCTOR | | | SIZE AND TYPE ALL LOCATED ON THE PLAN. INCLUDE A | | | SUMMARY LOAD CALCULATION SHOWING EXISTING ELECTRIC | | | SERVICE CAN HANDLE THE NEW LOADS; VERIFY SAFETY | | | CLEARANCES AND ACCESS. NEC 110.26, 215.5 | | | PROVIDE AN INTERSYSTEM BONDING TERMINAL. NEC 250.94 | | | PROVIDE FOR GFCI PROTECTION AT THE VENDING MACHINES. | | | NEC 422.51 | | | | | | NOTE: | | | SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE | | | ALARM SYSTEM, VOICE AND DATA. | | | | | | ROBERT LECKY, CBO | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | | | | |
|