Date Text
2012-04-09 11:32:516501 NORTH JOG ROAD
 PERMIT #12030781
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 TO PROTECT AGAINST WALL COLLAPSE, FIRE HYDRANTS SHALL
 BE LOCATED AT LEAST 40 FEET FROM THE BUILDING BEING
 PROTECTED PER NFPA 24.
  
 COULD NOT LOCATE THE CONTINUATION OF THE NEW 10" FIRE
 LINE ON SHEET 700-C3-015.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 OFFICE OF THE FIRE MARSHAL