| Plan Review Notes For Permit 12030778 |
| Permit Number |
12030778 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-10 14:05:49 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. INCORRECT CODE REFERENCE, FBC 2010 TOOK EFFECT ON | | | MARCH 15, 2012. REVISE PLAN. | | | | | | 2. INCORRECT EXPOSURE CLASSIFICATION. THIS PARCEL | | | APPEARS TO BE LOCATED IN EXPOSURE D. EITHER USE | | | EXPOSURE D OR ENGINEER IS TO PROVIDE AN AERIAL WITH A | | | WRITTEN JUSTIFICATION FOR EXPOSURE C. SEE FBC 1609.4.3. | | | | | | 3. INCLUDE WIND DESIGN CRITERIA ON REVISED PLAN FBC | | | 1603.1.4. | | | | | | 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB. | | | | | | |
|