2012-04-10 14:05:49****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2010
 FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL
  
 1. INCORRECT CODE REFERENCE, FBC 2010 TOOK EFFECT ON
 MARCH 15, 2012. REVISE PLAN.
  
 2. INCORRECT EXPOSURE CLASSIFICATION. THIS PARCEL
 APPEARS TO BE LOCATED IN EXPOSURE D. EITHER USE
 EXPOSURE D OR ENGINEER IS TO PROVIDE AN AERIAL WITH A
 WRITTEN JUSTIFICATION FOR EXPOSURE C. SEE FBC 1609.4.3.
  
 3. INCLUDE WIND DESIGN CRITERIA ON REVISED PLAN FBC
 1603.1.4.
  
 4. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB.
  
  