2012-08-10 12:37:222010 FBC
  
 DENIED BY BUILDING
  
 1) THE FLORIDA ENGINEER THAT SIGNED AND SEALED THE
 PLANS, LUIS LOPEZ P.E. #59805, VOLUNTARILY RELINQUISHED
 HIS LICENSE ON 4/27/2012 AND CAN NO LONGER CERTIFY
 PLANS AFTER THAT DATE. FS 471
  
 2) THE WINDSPEED SPECIFIED ON THE PLANS OF 160 MPH IS
 INCORRECT. THE CORRECT VULT WINDSPEED FOR THIS PROJECT
 IS 170 MPH PER 2010 FBC R301.2.1. PLEASE CORRECT.
  
 3) THE PRESCRIPTIVE ENERGY FORM 402-2010 CAN NOT BE
 USED FOR THIS PROJECT. THIS METHOD REQUIRES EACH
 COMPONENT TO MEET OR EXCEED EACH OF THE APPLICABLE
 PERFORMANCE CRITERIA. THE SHGC (SOLAR HEAT GAIN
 COEFFICIENT) FOR THE WINDOWS, THE WALL INSULATION AND
 CEILING INSULATION R-VALUES DO NOT MEET THE REQUIRED
 VALUES. FBC ENERGY CONSERVATION SECTION 402
  