2012-05-01 11:43:582010 FBC
  
 DENIED BY BUILDING
  
 1) THE APPLICATION DATE FOR THIS PERMIT IS MARCH 30,
 2012. THE 2010 FLORIDA BUILDING CODE BECAME EFFECTIVE
 ON MARCH 15, 2012. THEREFORE, THIS PROJECT IS REQUIRED
 TO COMPLY WITH THE 2010 FLORIDA BUILDING CODE. REVISE
 PLANS TO REFERENCE THE 2010 FBC AND ASCE 7-10.
  
 2) REVISE PLANS TO REFERENCE THE 2010 FBC DESIGN
 CRITERIA FOR WINDSPEEDS AND EXPOSURE CATEGORIES. FBC
 R301.1 AND R301.2.1.4.3
  
 3) REVISE THE OPENING DESIGN PRESSURES AS NECESSARY TO
 COMPLY WITH 2010 FBC SECTION R301.2.1.
  
 4) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT COMPLY
 WITH THE 2010 FBC FOR EXTERIOR DOORS, WINDOWS,
 STRUCTURAL MULLIONS AND STORM PANELS AS REQUIRED BY DCA
 RULE 9N-3.
  
 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 107.3.4.1
  
 6) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE NEW
 ROOM AS REQUIRED BY 2010 FBC ENERGY CONSERVATION
 SECTION 401.2.
  