| Notes |
| Date |
Text |
| 2012-05-01 11:43:58 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE APPLICATION DATE FOR THIS PERMIT IS MARCH 30, | | | 2012. THE 2010 FLORIDA BUILDING CODE BECAME EFFECTIVE | | | ON MARCH 15, 2012. THEREFORE, THIS PROJECT IS REQUIRED | | | TO COMPLY WITH THE 2010 FLORIDA BUILDING CODE. REVISE | | | PLANS TO REFERENCE THE 2010 FBC AND ASCE 7-10. | | | | | | 2) REVISE PLANS TO REFERENCE THE 2010 FBC DESIGN | | | CRITERIA FOR WINDSPEEDS AND EXPOSURE CATEGORIES. FBC | | | R301.1 AND R301.2.1.4.3 | | | | | | 3) REVISE THE OPENING DESIGN PRESSURES AS NECESSARY TO | | | COMPLY WITH 2010 FBC SECTION R301.2.1. | | | | | | 4) SUBMIT TWO SETS OF PRODUCT APPROVALS THAT COMPLY | | | WITH THE 2010 FBC FOR EXTERIOR DOORS, WINDOWS, | | | STRUCTURAL MULLIONS AND STORM PANELS AS REQUIRED BY DCA | | | RULE 9N-3. | | | | | | 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT. CITY AMENDMENTS 107.3.4.1 | | | | | | 6) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE NEW | | | ROOM AS REQUIRED BY 2010 FBC ENERGY CONSERVATION | | | SECTION 401.2. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|