Plan Review Notes
Plan Review Notes For Permit 12030754
Permit Number 12030754
Review Stop Z
Sequence Number 1
Notes
Date Text
2012-04-10 14:19:33FAILED
  
 PROVIDE RESPONSE IN WRITING.
  
 1) THE NORTHWOOD MIXED USE DISTRICT REGULATIONS REQUIRE
 THAT MECHANICAL SYSTEMS SHALL BE SCREENED FROM VIEW BY
 LANDSCAPING OR BUILT ELEMENTS DESIGNED AS AN INTEGRAL
 PART OF THE BUILDING ARCHITECTURE - SECTION
 94-213(D)(16) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS. INSUFFICIENT INFORMATION WAS PROVIDED TO
 VERIFY THAT THE PROPOSED 3.5 TON A/C UNIT LOCATED ON
 THE BUILDING'S ROOF WILL BE SCREENED. PROVIDE A CROSS
 SECTION, ELEVATION, SITE LINE DRAWING OR OTHER PLAN TO
 SHOW THE ROOF TOP EQUIPMENT COMPLIES WITH THE SCREENING
 REQUIREMENT.
  
 2) THE SPECIFICATIONS PROVIDED WITH THE PERMIT FOR THE
 A/C UNIT AND THE SUPPORT STAND INDICATE THAT THE STAND
 AND UNIT WILL 42 TO 72 INCHES IN HEIGHT, DEPENDING ON
 THE MODEL TYPE AND STAND CHOSEN.
  
 3) THE SUBMITTED PICTURES SHOW A PARAPET WITH NO
 DIMENSIONS, BUT WHICH APPEARS TO BE LESS THAN 30 INCHES
 HIGH, WHICH WOULD NOT SCREEN THE EQUIPMENT AND STAND
 MENTIONED IN #2 ABOVE.
  
 4) NO PLAN IS INCLUDED TO SHOW WHERE THE ROOF TOP A/C
 WILL BE MOUNTED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2012-04-05 11:58:27GIVEN TO ES