| Plan Review Notes For Permit 12030754 |
| Permit Number |
12030754 |
|
| Review Stop |
Z |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-10 14:19:33 | FAILED | | | | | | PROVIDE RESPONSE IN WRITING. | | | | | | 1) THE NORTHWOOD MIXED USE DISTRICT REGULATIONS REQUIRE | | | THAT MECHANICAL SYSTEMS SHALL BE SCREENED FROM VIEW BY | | | LANDSCAPING OR BUILT ELEMENTS DESIGNED AS AN INTEGRAL | | | PART OF THE BUILDING ARCHITECTURE - SECTION | | | 94-213(D)(16) OF THE ZONING AND LAND DEVELOPMENT | | | REGULATIONS. INSUFFICIENT INFORMATION WAS PROVIDED TO | | | VERIFY THAT THE PROPOSED 3.5 TON A/C UNIT LOCATED ON | | | THE BUILDING'S ROOF WILL BE SCREENED. PROVIDE A CROSS | | | SECTION, ELEVATION, SITE LINE DRAWING OR OTHER PLAN TO | | | SHOW THE ROOF TOP EQUIPMENT COMPLIES WITH THE SCREENING | | | REQUIREMENT. | | | | | | 2) THE SPECIFICATIONS PROVIDED WITH THE PERMIT FOR THE | | | A/C UNIT AND THE SUPPORT STAND INDICATE THAT THE STAND | | | AND UNIT WILL 42 TO 72 INCHES IN HEIGHT, DEPENDING ON | | | THE MODEL TYPE AND STAND CHOSEN. | | | | | | 3) THE SUBMITTED PICTURES SHOW A PARAPET WITH NO | | | DIMENSIONS, BUT WHICH APPEARS TO BE LESS THAN 30 INCHES | | | HIGH, WHICH WOULD NOT SCREEN THE EQUIPMENT AND STAND | | | MENTIONED IN #2 ABOVE. | | | | | | 4) NO PLAN IS INCLUDED TO SHOW WHERE THE ROOF TOP A/C | | | WILL BE MOUNTED. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1446. | | 2012-04-05 11:58:27 | GIVEN TO ES |
|