| Plan Review Notes For Permit 12030709 |
| Permit Number |
12030709 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-02 10:21:45 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. THIS APPEARS TO BE LOCATED IN EXPOSURE C, SEE FBC R | | | 301.2.1.4.3. | | | | | | 2. BUILDING DATA FOR DESIGN PRESSURES IS INCOMPLETE; | | | MEAN ROOF HEIGHT, ETC. NOT PROVIDED. | | | | | | 3. TWO SETS OF THE INSTALLATION SCHEDULE ARE REQUIRED. | | | FAILURE TO PROVIDE TWO SETS MAY RESULT IN ISSUANCE | | | DELAYS. | | | | | | 4. PLEASE SEE PRODUCT APPROVAL FOR REQUIRED EDGE | | | DISTANCE FOR ZONE 4 INSTALLATIONS, SEE ALSO FBC | | | RESIDENTIAL 301.2.1.2.1. PLEASE REVISE INSTALLATION | | | SCHEDULE. | | | | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ | | | INSTALLATION.PDF | | | | | | | | | | | | |
|