Plan Review Notes
Plan Review Notes For Permit 12030695
Permit Number 12030695
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-17 16:53:352010 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE APPLICATION DATE FOR THIS PERMIT WAS MARCH 28,
 2012. THE 2010 FBC BECAME EFFECTIVE ON MARCH 15, 2012.
 THEREFORE, THE PLANS ARE REQUIRED TO COMPLY WITH THE
 2010 FBC. PLEASE REVISE THE PLANS TO REFERENCE THE 2010
 FBC RATHER THAN THE 2007 FBC.
  
 2) PLEASE REVISE THE BUILDING INFORMATION ON SHEET CV,
 WHICH IS INCORRECT. THE STRUCTURE IS TWO STORIES AND
 THE BUILDING HEIGHT IS MORE THAN 12 FEET. FBC R301.2.1
  
 3) PLEASE REVISE THE DRAWING INDEX ON SHEET CV, WHICH
 IS INCORRECT. SHEET A3 IS THE DECK PLAN, SHEET A4 IS
 THE ELECTRICAL PLAN AND THERE WASN'T A MECHANICAL PLAN.
 FBCR M1401.3 AND FBCR M1601.1
  
 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW
 EXTERIOR DOOR AS REQUIRED BY DCA RULE 9N-3.
  
 5) SPECIFY THE MINIMUM REQUIRED EMBED DEPTH FOR THE
 WEDGE ANCHORS AT THE WOOD DECK. FBC R301.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]