| Plan Review Notes For Permit 12030695 |
| Permit Number |
12030695 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-17 16:53:35 | 2010 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | 1) THE APPLICATION DATE FOR THIS PERMIT WAS MARCH 28, | | | 2012. THE 2010 FBC BECAME EFFECTIVE ON MARCH 15, 2012. | | | THEREFORE, THE PLANS ARE REQUIRED TO COMPLY WITH THE | | | 2010 FBC. PLEASE REVISE THE PLANS TO REFERENCE THE 2010 | | | FBC RATHER THAN THE 2007 FBC. | | | | | | 2) PLEASE REVISE THE BUILDING INFORMATION ON SHEET CV, | | | WHICH IS INCORRECT. THE STRUCTURE IS TWO STORIES AND | | | THE BUILDING HEIGHT IS MORE THAN 12 FEET. FBC R301.2.1 | | | | | | 3) PLEASE REVISE THE DRAWING INDEX ON SHEET CV, WHICH | | | IS INCORRECT. SHEET A3 IS THE DECK PLAN, SHEET A4 IS | | | THE ELECTRICAL PLAN AND THERE WASN'T A MECHANICAL PLAN. | | | FBCR M1401.3 AND FBCR M1601.1 | | | | | | 4) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE NEW | | | EXTERIOR DOOR AS REQUIRED BY DCA RULE 9N-3. | | | | | | 5) SPECIFY THE MINIMUM REQUIRED EMBED DEPTH FOR THE | | | WEDGE ANCHORS AT THE WOOD DECK. FBC R301.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|