2012-04-02 16:31:57BUILDING PLAN REVIEW
 PERMIT: 12030659
 ADD: 1020 CHAROLETTE AVE
 CONT: HOLT CONTRACTORS
 TEL: (561)2129099
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) CONTRACTOR TO TAKE RESPONSIBILITY FOR THEIR PLANS.
 PRINT THEIR NAME, SIGN THEIR NAME AND LICENSE NUMBER ON
 THE PLANS. @007/09 FBC-B 106.1.
  
 2) MISSING INFORMATION ON WALL SECTION A-A:
 2A) PLANS DO NOT IDENTIFY THE TYPE OF LEDGER ATTACHED
 TO THE BLOCK WALL.
 2B) PLANS DO NOT IDENTIFY THE TYPE OF ANCHOR, DIAMETER,
 LENGTH NOR SPACING.
 2C) PLANS DO NOT IDENTIFY THE TYPE OF BUCKET OR HANGER
 USED TO HANG THE 2 X 10'S.
 2D) PLANS DO NOT INDICATE NEITHER TOP NOR BOTTOM PLATES
 NOR THE ANCHORING OF THE BOTTOM PLATE TO THE CONCRETE
 FLOOR.
 2E) PLANS DO NOT INDICATE IF THE NEWLY FORMED SPACE
 ABOVE THE NEW ROOM WILL BE USED FOR A MEZZANINE FOR
 STORAGE, IF SO PROVIDE THE DESIGNED STORAGE IN PSF.
 FBC-B 1104.1-2.
 2F) TO THE CODE EDITION THIS PLAN WAS DESIGNED TOO.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER